Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06CM06303
Permit Details
Apply Date:
12/13/2006
Applicant:
N/A
Description:
SITE AND NEW RETAIL SHELL BUILDING
Architects:
- KRAMER, JOEL ERIC
Contractors:
- SUN WESTERN CONTRACTORS
Permit Reviews
Permit Number - T06CM06303
Permit Status: Final
Permit Description: SITE AND
NEW RETAIL SHELL BUILDING
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
04/13/2007 | RESUBMITTAL - SITE ALL | 04/23/2007 | COMPLETED |
04/23/2007 | RESUBMITTAL - SITE ALL | 06/12/2007 | COMPLETED |
05/10/2007 | PLANS OK TO SUBMIT - 3RD PARTY | 09/10/2007 | COMPLETED |
06/29/2007 | RESUBMITTAL - SITE | 08/10/2007 | COMPLETED |
08/21/2007 | RESUBMITTAL - SITE | 09/06/2007 | COMPLETED |
08/24/2007 | 3RD PARTY REVIEW-COMMERCIAL | 11/05/2007 | COMPLETED |
09/06/2007 | RESUBMITTAL - SITE | 10/04/2007 | COMPLETED |
10/04/2007 | RESUBMITTAL - SITE | 10/11/2007 | COMPLETED |
10/17/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 08/27/2009 | COMPLETED |
11/05/2007 | POST 3RD PARTY REVIEW | 12/04/2007 | COMPLETED |
12/04/2007 | RESUBMITTAL | 12/19/2007 | COMPLETED |
12/13/2006 | PLANS OK TO SUBMIT - SITE | 12/13/2006 | COMPLETED |
12/13/2006 | SITE | 02/22/2007 | COMPLETED |
12/19/2007 | RESUBMITTAL | 02/11/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM06303
Permit Status: Final
Permit Description: SITE AND
NEW RETAIL SHELL BUILDING
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/13/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06CM06303
Permit Description: SITE AND
NEW RETAIL SHELL BUILDING
Total Completed Inspections - 33
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
05/01/2008 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
05/05/2008 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
05/06/2008 | PLUMBING - YARD WTR LINE/TEST | BBENEDON | Approved | IVRS - Inspection :* |
05/07/2008 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
05/14/2008 | SITE - SEWER | BBENEDON | Approved | IVRS - Inspection :* |
09/02/2008 | ELECTRIC - OUTDOOR LIGHTING | RJIROUDE | Approved | IVRS - Inspection :* 1. OK 2 - 4" PVC FROM TEP XFMR TO SES 2. CALL DEVELOPMENT SERVICES HAVE 02010 ELECTRIC UNDERGROUND ADDED TO PERMIT 3. HAVE ENGINEER REVISE PLAN FOR SERVICE CONDUCTORS PLAN SHOWS 2 SETS OF 3 - 350MEM AND INDICATES 30 4W SERVICE. ENGINEER MISSING A CONDUCTOR ON SERVICE 4. INSTALL WARNING RIBBON ABOVE SERVICE RACEWAYS PER NEC 300.5 |
09/02/2008 | ELECTRIC - CABLE DROP | RJIROUDE | Approved | IVRS - Inspection :* |
09/25/2008 | STEM WALL/RETAINING WALL | GDABBS | Approved | IVRS - Inspection :* MAIN BUILDING STEM WALL ONLY - OK TO GROUT SPECIAL INSPECTION COMPLETED |
09/30/2008 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* |
10/03/2008 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* 1. YARD WATER OK 2. NEED TO SEE IRRIGATION CONNECTION AND BACKFLOW ASSEMBLY 3. RWLS REQUIRE DRAINAGE FITTINGS, TEST AND PROTECTION FROM CONCRETE. - ALSO, SUPPORT AND USE NEW PIPING THAT IS NOT SUN DAMAGED |
10/06/2008 | ELECTRIC - UFER | RJIROUDE | Approved | IVRS - Inspection :* |
10/14/2008 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* TRASH ENCLOSURE & NORTH SCREEN WALL FOOTINGS OK TO POUR |
10/17/2008 | REINFORCED MASONRY PRE-GROUT | JBURGE | Approved | IVRS - Inspection :* PERIMETER WALLS TOPPED OUT AT 20'-24'4" GROUTED |
11/10/2008 | EXT METAL CLIPS/EXT SHEATHING | JBURGE | Approved | NE SHEAR WALL @ ROOF LEVEL |
11/14/2008 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :* OK TO COVER -- CRICKETS IN PLACE |
11/20/2008 | PLUMBING - PRE SLAB | BBENEDON | Approved | IVRS - Inspection :* |
11/20/2008 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
12/01/2008 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* RD's BELOW SLAB W/TEST OK |
12/01/2008 | BUILDING PRE-SLAB | JBURGE | Approved | IVRS - Inspection :* OK TO POUR SLAB |
12/10/2008 | ELECTRIC - INTERMEDIATE | RMORENO | Approved | IVRS - Inspection :* BOX WITH MC ON FRONT NORTH WALL AND WEST WALL BOTH BOXES -- OK FOR SIGNS |
12/12/2008 | PLUMBING - SEWER HCS CONNECT | BBENEDON | Approved | IVRS - Inspection :* |
01/14/2009 | FRAMING | JBURGE | Approved | IVRS - Inspection :* |
02/13/2009 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
02/19/2009 | STUCCO MESH | JBURGE | Approved | IVRS - Inspection :* OK TO STUCCO EXTERIOR |
03/05/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED FOR METERS 100,110,120,130 & HOUSE PANEL PER R. MORENO |
07/13/2009 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK |
07/13/2009 | OUTDOOR LIGHTING FINAL | RMORENO | Approved | |
07/13/2009 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection :* |
08/24/2009 | NPPO - FINAL | ACONNOR | Approved | |
08/24/2009 | LANDSCAPE - FINAL | ACONNOR | Approved | |
08/24/2009 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* |
08/26/2009 | FIRE - FINAL | LTHOMAS | Approved |