Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06303
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/06/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUITE D -- NEED KNOCKOUT SEALS SUITE C -- MC IN CHANNEL OF STUD SUITE B -- MC IN CHANNEL OF STUD & LOOSE CONNECTORS SUITE A -- 4/4SQ BOX MISSING KNOCKOUT SEAL/NO GROUNDS |
|
12/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BOX WITH MC ON FRONT NORTH WALL AND WEST WALL BOTH BOXES -- OK FOR SIGNS |
|
10/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK GROUND RODS 2. TEMP CONST. POWER NEEDS TO BE ADDED TO PERMIT AND NEEDS TO BE OUTSIDE BUILDING |
|
09/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 5 - 2" PVC FROM SES TO PANEL LOCATIONS 2. WHY WAS UFER NEVER INSTALLED. UFER TO BE INSTALLED. SEE NEC 250.50 |