Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
Permit Number - T06CM06303
Inspection Description - ELECTRIC - OUTDOOR LIGHTING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2009 | ELECTRIC - OUTDOOR LIGHTING | Approved | ||
03/02/2009 | ELECTRIC - OUTDOOR LIGHTING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/02/2008 | ELECTRIC - OUTDOOR LIGHTING | Not ready for Inspection | IVRS - Inspection :* 1. OK 2 - 4" PVC FROM TEP XFMR TO SES 2. CALL DEVELOPMENT SERVICES HAVE 02010 ELECTRIC UNDERGROUND ADDED TO PERMIT 3. HAVE ENGINEER REVISE PLAN FOR SERVICE CONDUCTORS PLAN SHOWS 2 SETS OF 3 - 350MEM AND INDICATES 30 4W SERVICE. ENGINEER MISSING A CONDUCTOR ON SERVICE 4. INSTALL WARNING RIBBON ABOVE SERVICE RACEWAYS PER NEC 300.5 |
|
08/29/2008 | ELECTRIC - OUTDOOR LIGHTING | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* NO PLANS ON SITE. NO CONTRACTOR ON SITE. IF LOOKING FOR UNDERGROUND INSPECTION SCHEDULE PROPER INSPECTION ITEM |
|
08/21/2008 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* OK 5 - 3/4" PVC UNDER SLAB 60' HEADING NORTH |