Permit: T06CM06303

Parcel: 13325183B


Addresses:

8650 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06303

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
07/08/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED TO SEE DOCUMENTATION FOR STERILIZATION AND CLEAN WATER REPORT
2) ASLO PVB UPSTRM CONN.
3) EXT. CLEANOUT UNDER FRANK P COVER IS MISSING PLUG
05/18/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE PREVIOUSLY NOTED ITEMS AND PROVIDE DOCUMENTATION - EXPOSE UPSTRM CONN. AT PVB CERT. REQUIRED
03/23/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
YARD WATER TO IRR.
OK RECALL FOR INSPECTION OF RPA INSTALL
PVB REQUIRES TEST AND CERT
03/20/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE TEST AND TRACER WIRE ON YARD WATER TO IRR.
ALSO, BACKFLOW PREVENTOR
03/17/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE SITE WORK
IRRIGATION BACKFLOW W/CERT. C.O.'s
STERILIZE WATER SYSTEM PER UPC 609
CORRECT DRIPS ON LAVS
02/05/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
ROOF PENETRATIONS REQUIRE AN APPROVED FLUSHING
10' FROM OR 3' ABOVE FORCED AIR INTAKE FOR VTR
PAINT FOR UV PROTECTION