Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address:
4240 N 1ST AV
Address NEW:
4240 N 1ST AV
Apply Date:
03/31/2006
Applicant:
NOAH BURCH
Description:
NEW:FITNESS CENTER TCO FOR MAIN BUILDING
Architects:
  • UNTI, HARVEY GEORGE
Contractors:
  • SEPULVEDA COMMERCIAL DEVELOPMENT INC

Permit Reviews

Permit Number - T06CM01833
Permit Status: C of o
Permit Description: NEW:FITNESS CENTER TCO FOR MAIN BUILDING
Start Date Submittal Complete Date Status  
03/31/2006 PLANS OK TO SUBMIT - COMM 04/13/2006 COMPLETED Review Details
04/13/2006 3RD PARTY REVIEW-COMMERCIAL 07/26/2006 COMPLETED Review Details
07/26/2006 POST 3RD PARTY REVIEW 08/04/2006 COMPLETED Review Details
08/04/2006 RESUBMITTAL 08/21/2006 COMPLETED Review Details
08/08/2006 SITE 08/22/2006 COMPLETED Review Details
08/21/2006 RESUBMITTAL 08/22/2006 COMPLETED Review Details
12/01/2006 3RD PARTY REVIEW-REVISION/OTHER 12/14/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM01833
Permit Status: C of o
Permit Description: NEW:FITNESS CENTER TCO FOR MAIN BUILDING
Total Outstanding Activity Conditions - 1
Date Name
03/31/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T06CM01833
Permit Description: NEW:FITNESS CENTER TCO FOR MAIN BUILDING
Total Completed Inspections - 46
Date Description Inspector Results Comments
08/31/2006 ELECTRIC - UFER LHANLY Approved G.E. #1 OK-- APPROX 40' OF #1 STRANDED CU CLAMPED BOTH ENDS AND TIED REG INTERVALS. GRID C/16
09/05/2006 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
INTERIOR COLUMN OK
09/14/2006 STEM WALL/RETAINING WALL AQUIROZ Approved IVRS - Inspection :*
EXTERIOR STEM ONLY
09/27/2006 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
1. CORRECTIONS MADE OK
CONTRACTOR TO REDLINE ALL CHANGES TO THE PLAN.
2. OK TO BACKFILL
11/08/2006 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection :*
12/06/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
INSPECTION FOR SECONDARY TRENCH ONLY

INSTALL WARNING RIBBON MIN. 12" ABOVE SECONDARY RACEWAYS BEFORE YOU BACKFILL -- NEC 300.5
12/15/2006 ROOF NAILING LHANLY Approved IVRS - Inspection :*
MAIN ROOF OK
ROTUNDA BASE STEEL OK
I ONLY NEED TO SEE SP. INSP. FOR WELDS & 45 BOLTS
12/26/2006 FRAMING JBURGE Approved IVRS - Inspection :*
J/7.5 TO L/7.5; L/7.5 TO L/10.5, L/10.5 TO J/10.5
OK TO SHEETROCK ONE SIDE

BASKETBALL COURT WALLS - PLANS (PAGE A2.0 - KEY NOTES) CALL FOR RED IRON METAL STUDS - NEED AN RFI FROM ENGINEER APPROVING USE OF 16 GA. METAL STUDS - DO NOT COVER UNTIL APPROVED.
12/27/2006 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
FRONT ENTRY OK
REAR ELEC. ROOM OK
12/27/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
RMS 122, 120, 117, MEZZ 203, 202, 204
OK TO COVER
12/28/2006 PLUMBING - ROOF DRAINS RMYERS Approved IVRS - Inspection :*
1. WATER TEST ON INTERIOR RAIN LEADERS OK
2. NEED TO SEE RECONNECTION TO U.G AT TEST
01/30/2007 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
02/05/2007 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
03/20/2007 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
04/03/2007 ELECTRIC - TEMPORARY SERVICE CCLEMENS Approved IVRS - Inspection :*
STILL NEED TO LOOK @ PIPE BONDING AND TRANSFORMER
AND FEEDERS.

DO NOT ENERGIZE ANY LOAD SIDE EQUIPMENT BEFORE APPROVAL KEEP SERVICE LOCKED AND SERVICE DISCONNECTS OFF.

RECEIVED PERFORMANCE TEST LETTER TODAY
04/04/2007 TEP CLEARANCE - AM BFLORES Approved TEC PER C.CLEMENS
04/13/2007 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
04/18/2007 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
PUNCH LIST WALK THRU WITH CONTRACTOR
04/18/2007 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
04/20/2007 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
04/20/2007 FIRE SPKLR - FINAL LTHOMAS Approved
04/20/2007 FIRE - FINAL LTHOMAS Approved
04/20/2007 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
04/20/2007 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
04/23/2007 SITE - SEWER RMYERS Approved IVRS - Inspection :*
04/23/2007 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
04/23/2007 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
04/23/2007 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
04/26/2007 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
04/26/2007 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
04/26/2007 OUTDOOR LIGHTING FINAL CCLEMENS Approved IVRS - Inspection :*
04/26/2007 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :*
05/01/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
05/03/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
OK C OF O
05/03/2007 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
CHECK WATER HEATER VENTS
05/03/2007 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
05/07/2007 RIGHT OF WAY - FINAL MOTERO Approved
05/07/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved
05/07/2007 MECHANICAL - INTERMEDIATE JMILITEL Approved
05/07/2007 NPPO - FINAL ACONNOR Approved
05/07/2007 LANDSCAPE - FINAL ACONNOR Approved
05/07/2007 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
05/07/2007 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved
05/11/2007 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
CORRECTION MADE OK
OK FOR C OF O
05/17/2007 ENGINEERING - FINAL MRUSSO Approved PER INSP CARD
05/18/2007 PERMIT FINALED MOTERO Approved