Permit: T06CM01833

Parcel: 10510097A


Addresses:

4240 N 1ST AV

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
04/23/2007 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
04/18/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
04/03/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
CLOSET FLANGES OK
04/02/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
03/30/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1. CLOSET FLANGES TO EXTEND TO A QUARTER INCH ABOVE FINISHED FLOOR.
2. SEE NOTES FROM 03/21/07
03/23/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
SCREW FLANGES TO FLOOR
03/21/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
CLOSET FLANGE INSP. DENIED
SEE CODE SECTIONS 316.3.1 AND 704.4.4
ALSO, SEE ABS INSTALLATION STANDARD #5 SEC. 314.2 ON
PG 342

YOU HAVE INSTALLED A 3" CLOSET FLANGE INSIDE A 4" PIPE
PROVIDE LISTING FOR THIS INSTALLATION
03/14/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
WATERPROOFING MENS SHOWER OK
03/12/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
WOMENS LOCKER ROOM SHOWER PANS WATERPROOFED OK