Permit: T06CM01833

Parcel: 10510097A


Addresses:

4240 N 1ST AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/03/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CHECK WATER HEATER VENTS
04/20/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :* OK FOR TCO
04/19/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
VENTS ON CONDENSATE DRAINS MUST BE DOWNSTREAM OF THE TRAP. INSULATE SPIRAL PIPE IN STORAGE ROOM & AT FIRE DAMPER ABOVE MEZZANINE.
UNIT #14 MISSING ELEC. SERVICE PANEL
TESTED FIRE DAMPERS & DUCT DETECTORS
OK TO FILE FOR TEMP C OFO
04/17/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE FIRE DAMPER ACCESS DOORS & DUCT SMOKE DETECTORS TO ACTIVATE THE DAMPERS.