Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM01833
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. INSTALL MAIN BONDING BUSS - NEC 250.28 2. PROVIDE PERFORMANCE TEST FOR SERVICE - NEC 230.95C RECEIVED CERTIFICATION LETTER FROM G.E AND TORQUE LETTER TODAY. 3. TERMINATE ALL FEEDERS AND TRANSFORMER SECONDARYS 4. FINISH METAL PIPE BONDING OK CEILING COVER UNDER MEZZANINE |
|
03/30/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/28/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER JUICE BAR/KITCHEN AREA |
|
03/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER DIRECTLY ABOVE 2ND LEVEL MEZZANINE BOB 977-6344 |
|
03/23/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | ||
03/22/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK CEILING COVER WOMENS LOCKER ROOM 2. OK CEILING COVER ROTUNDA AND MAIN FLOOR UP TO 2ND LEVEL. 3. STAIR RAILINGS ONLY |
|
03/21/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RACEWAYS FOR SAUNA FEEDERS ARE OVERFILLED - NEC ANNEX C 2. NEUTRALS TO BE WHITE ENTIRE LENGTH -- NEC 200.6 3. FIRE ALARM WIRING TO BE NEAT AND WORKMAN LIKE MANNER -- PROPERLY STRAPPED -- IN ALL AREAS. 4. GRID SUPPORT WIRES NOT TO SUPPORT EQUIPMENT NEC 300.11 5. NEED SUPPORT WIRES ON ALL FIXTURES 6. FINISH WIRING, REMOVE TEMP WIRING, CHECK FOR PREVIOUS VIOLATIONS. |
|
03/19/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY TEST SWITCHES TO BE CUT IN. 2. ALL EQUIPMENT GROUNDS TO BE CONNECTED AND CONNECTORS USE AS LISTED. 3. SEAL ALL UNUSED OPENINGS IN BOXES AND RACEWAYS. 4. PROVIDE ACCESS TO ALL BOXES |
|
03/16/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER - SPECIAL EXERCISE, MEN'S LOCKER ROOM, FREE WEIGHT AREA *NOTE: ALL LOW VOLTAGE/DATA WIRING TO BE COMPLETE FOR CEILING INSPECTIONS. |
|
03/15/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS CHECK FOR: BOX FILL PROPER USE OF WIRENUTS PROPER TERMINATION OF GROUNDS CONTINUITY (BONDING OF RACEWAYS OVER 250V REMOVE TEMP WIRING) |
|
03/13/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/12/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER SPINNING (BIKE ROOM) |
|
03/07/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/05/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/01/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RM 118 OK KIDS CLUB FINISH FIRE ALARM INSTALLATION |
|
02/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK POWER FOR TV'S ON STAIR LANDING CEILING 2. OK LIGHTING MEZZ STAIRS TO O/S SW EXIT 3. OK RACQUET BALL COURTS 2 & 5 FOR CEILING 4. OK ROTUNDA CAN LIGHTS AT ENTRY 5. SUPPORT FRONT EXTERIOR CAN LIGHTS ON MC WITHIN 12" OF CANS, BEFORE COVERING. |
|
02/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SECURE SUPPORT WIRES @ BOTH ENDS OK CEILING COVER IN AEROBICS ROOM AFTER CORRECTION NOTE: DO NOT COVER AREAS BEFORE INSPECTION |
|
02/22/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED BOX - NEC 314 2. HAVE IMPROPER CLAMP TO BUILDING STEEL - NEC 110.3 3. SECURE RACEWAYS @ TWO ENDS - NEC 300.11 |
|
02/21/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* DO NOT CALL BEFORE READY FOR INSPECTION FEE MAY BE CHARGED |