Permit: T06CM01833

Parcel: 10510097A


Addresses:

4240 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM01833

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/02/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. INSTALL MAIN BONDING BUSS - NEC 250.28
2. PROVIDE PERFORMANCE TEST FOR SERVICE - NEC 230.95C
RECEIVED CERTIFICATION LETTER FROM G.E AND TORQUE LETTER TODAY.
3. TERMINATE ALL FEEDERS AND TRANSFORMER SECONDARYS
4. FINISH METAL PIPE BONDING

OK CEILING COVER UNDER MEZZANINE
03/30/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/28/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER JUICE BAR/KITCHEN AREA
03/27/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER DIRECTLY ABOVE 2ND LEVEL MEZZANINE
BOB 977-6344
03/23/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection
03/22/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK CEILING COVER WOMENS LOCKER ROOM
2. OK CEILING COVER ROTUNDA AND MAIN FLOOR UP
TO 2ND LEVEL.
3. STAIR RAILINGS ONLY
03/21/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RACEWAYS FOR SAUNA FEEDERS ARE OVERFILLED -
NEC ANNEX C
2. NEUTRALS TO BE WHITE ENTIRE LENGTH -- NEC 200.6
3. FIRE ALARM WIRING TO BE NEAT AND WORKMAN LIKE MANNER -- PROPERLY STRAPPED -- IN ALL AREAS.
4. GRID SUPPORT WIRES NOT TO SUPPORT EQUIPMENT
NEC 300.11
5. NEED SUPPORT WIRES ON ALL FIXTURES
6. FINISH WIRING, REMOVE TEMP WIRING, CHECK FOR PREVIOUS VIOLATIONS.
03/19/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMERGENCY TEST SWITCHES TO BE CUT IN.
2. ALL EQUIPMENT GROUNDS TO BE CONNECTED AND CONNECTORS USE AS LISTED.
3. SEAL ALL UNUSED OPENINGS IN BOXES AND RACEWAYS.
4. PROVIDE ACCESS TO ALL BOXES
03/16/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER - SPECIAL EXERCISE, MEN'S LOCKER ROOM, FREE WEIGHT AREA

*NOTE: ALL LOW VOLTAGE/DATA WIRING
TO BE COMPLETE FOR CEILING INSPECTIONS.
03/15/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
CHECK FOR:
BOX FILL
PROPER USE OF WIRENUTS
PROPER TERMINATION OF GROUNDS
CONTINUITY (BONDING OF RACEWAYS OVER 250V REMOVE TEMP WIRING)
03/13/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/12/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER SPINNING (BIKE ROOM)
03/07/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/05/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/01/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
RM 118 OK
KIDS CLUB
FINISH FIRE ALARM INSTALLATION
02/27/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK POWER FOR TV'S ON STAIR LANDING CEILING
2. OK LIGHTING MEZZ STAIRS TO O/S SW EXIT
3. OK RACQUET BALL COURTS 2 & 5 FOR CEILING
4. OK ROTUNDA CAN LIGHTS AT ENTRY
5. SUPPORT FRONT EXTERIOR CAN LIGHTS ON MC WITHIN 12" OF CANS, BEFORE COVERING.
02/23/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
SECURE SUPPORT WIRES @ BOTH ENDS
OK CEILING COVER IN AEROBICS ROOM AFTER CORRECTION

NOTE: DO NOT COVER AREAS BEFORE INSPECTION
02/22/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OVERFILLED BOX - NEC 314
2. HAVE IMPROPER CLAMP TO BUILDING STEEL - NEC 110.3
3. SECURE RACEWAYS @ TWO ENDS - NEC 300.11
02/21/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
DO NOT CALL BEFORE READY FOR INSPECTION
FEE MAY BE CHARGED