Permit: T06CM01105
Permit Details
Apply Date:
02/23/2006
Applicant:
N/A
Description:
TI:RETAIL
Contractors:
- EMORY ELECTRICAL CONTRACTOR,*C
Permit Reviews
Permit Number - T06CM01105
Permit Status: Expired
Permit Description: TI:RETAIL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/23/2006 | COMMERCIAL TI | 02/28/2006 | COMPLETED |
| 02/28/2006 | COMMERCIAL TI | 03/06/2006 | COMPLETED |
| 04/13/2006 | RESUBMITTAL | 05/31/2006 | COMPLETED |
| 05/31/2006 | RESUBMITTAL | 06/15/2006 | COMPLETED |
| 06/15/2006 | OTHER | 06/15/2006 | COMPLETED |
| 11/14/2006 | OTHER | 11/14/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM01105
Permit Status: Expired
Permit Description: TI:RETAIL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/23/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06CM01105
Permite Description: TI:RETAIL
Total Outstanding Inspections - 10
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| EXCAVATION/LAYOUT REBAR & ZON | N/A | Not Inspected | ||
| BUILDING PRE-SLAB | N/A | Not Inspected | ||
| BUILDING - FINAL | N/A | Not Inspected | ||
| ELECTRIC - CABLE DROP | N/A | Not Inspected | ||
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| MECHANICAL - HOOD SYSTEMS | N/A | Not Inspected | ||
| FIRE - FINAL | N/A | Not Inspected | ||
| 07/20/2006 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* 1. BOND SERVICE RACEWAYS - NEC 250.92 2. PROVIDE BUSHING FOR #4 AND LARGER CONDUCTOR - NEC 300.4 (F) 3. BOND EQUIPMENT PER NEC 250.6 4. SIZE BONDING JUMPERS PER NEC 250.102 (C) 5. BOND ALL STEEL AND METAL PIPING -- 250.104 OK TO COVER SECONDARY DITCH |
| 08/03/2006 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* 1) MAKE SURE ALL PIPING SYSTEMS ARE BONDED TO SERVICE INCLUDING WATER AND COMPRESSED AIR NEC 250.104 |
| 09/15/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE PAPERWORK FOR #5 NONE OF YOUR NEW MACHINERY IS LISTED OR LABELED BY AN APPROVED TESTING FACILITY AS REQUIRED BY THE 2002 NATIONAL ELECTRICAL CODE 110 - 2, 3 |
Completed Inspections
Permit Status: Expired
Permit Number: T06CM01105
Permit Description: TI:RETAIL
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 08/07/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER C. CLEMENS |
| 08/22/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |