Permit: T06CM01105

Parcel: 11308011B


Addresses:

3110 N 1ST AV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
07/20/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. BOND SERVICE RACEWAYS - NEC 250.92
2. PROVIDE BUSHING FOR #4 AND LARGER CONDUCTOR -
NEC 300.4 (F)
3. BOND EQUIPMENT PER NEC 250.6
4. SIZE BONDING JUMPERS PER NEC 250.102 (C)
5. BOND ALL STEEL AND METAL PIPING -- 250.104

OK TO COVER SECONDARY DITCH