Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. BOND SERVICE RACEWAYS - NEC 250.92 2. PROVIDE BUSHING FOR #4 AND LARGER CONDUCTOR - NEC 300.4 (F) 3. BOND EQUIPMENT PER NEC 250.6 4. SIZE BONDING JUMPERS PER NEC 250.102 (C) 5. BOND ALL STEEL AND METAL PIPING -- 250.104 OK TO COVER SECONDARY DITCH |