Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE PAPERWORK FOR #5 NONE OF YOUR NEW MACHINERY IS LISTED OR LABELED BY AN APPROVED TESTING FACILITY AS REQUIRED BY THE 2002 NATIONAL ELECTRICAL CODE 110 - 2, 3 |
|
| 08/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED PROTECTIVE BUSHING FOR ALL CONDUCTORS #4 & LARGER NEC 300.4 (F) 2. SECURE EMT EVERY 10' AND WITHIN 3' OF ENTRY - NEC 358.30 (A) 3. HAVE UNDERSIZED EQUIPMENT GROUND FOR BANDER & FUTURE DISCONNECT AND PUMP TRANSFORMERS - NEC 250.122 4. TIGHTEN ALL FITTING & THEIR SET SCREWS -- NEC 110 5. EQUIPMENT HAS DIFFERENT VOLTAGE WIRED TO IT THAN WHAT IS ON LISTING LABEL - NEC 110.3 6. EQUIPMENT (ALL) REQUIRES A DISCONNECT - NEC 430.74 7. WATER BOND UNDERSIZED - NEC 250.104 8. FLEX NEEDS PROPER SECURE/SUPPORT/PROTECTION NEC 350.12(1) & 350.30 9. PLUG ALL HOLES IN EQUIPMENT - NEC 110 10. USE EQUIPMENT GROUND TO GROUND ALL METAL ENCLOSURES. |