Permit: T06CM01105

Parcel: 11308011B


Addresses:

3110 N 1ST AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE PAPERWORK FOR #5
NONE OF YOUR NEW MACHINERY IS LISTED OR LABELED BY AN APPROVED TESTING FACILITY AS REQUIRED BY THE
2002 NATIONAL ELECTRICAL CODE 110 - 2, 3
08/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED PROTECTIVE BUSHING FOR ALL CONDUCTORS #4 & LARGER NEC 300.4 (F)
2. SECURE EMT EVERY 10' AND WITHIN 3' OF ENTRY -
NEC 358.30 (A)
3. HAVE UNDERSIZED EQUIPMENT GROUND FOR BANDER & FUTURE DISCONNECT AND PUMP TRANSFORMERS -
NEC 250.122
4. TIGHTEN ALL FITTING & THEIR SET SCREWS -- NEC 110
5. EQUIPMENT HAS DIFFERENT VOLTAGE WIRED TO IT THAN WHAT IS ON LISTING LABEL - NEC 110.3
6. EQUIPMENT (ALL) REQUIRES A DISCONNECT - NEC 430.74
7. WATER BOND UNDERSIZED - NEC 250.104
8. FLEX NEEDS PROPER SECURE/SUPPORT/PROTECTION
NEC 350.12(1) & 350.30
9. PLUG ALL HOLES IN EQUIPMENT - NEC 110
10. USE EQUIPMENT GROUND TO GROUND ALL METAL ENCLOSURES.