Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address NEW:
1010 N ALVERNON WY
Apply Date:
11/17/2005
Applicant:
JIM WATSON
Description:
TI:CHURCH
Contractors:
  • BARKER MORRISSEY CONTRACTING INC

Permit Reviews

Permit Number - T05CM05786
Permit Status: C of o
Permit Description: TI:CHURCH
Start Date Submittal Complete Date Status  
01/23/2006 RESUBMITTAL - SITE ALL 06/26/2006 COMPLETED Review Details
02/13/2007 REVISION - - 2ND 02/14/2007 COMPLETED Review Details
06/26/2006 RESUBMITTAL - SITE ALL 08/22/2006 COMPLETED Review Details
06/26/2006 PLANS OK TO SUBMIT - 3RD PARTY 06/26/2006 COMPLETED Review Details
06/26/2006 3RD PARTY REVIEW-COMMERCIAL TI 07/13/2006 COMPLETED Review Details
07/13/2006 POST 3RD PARTY REVIEW 08/29/2006 COMPLETED Review Details
11/06/2006 3RD PARTY REVIEW-REVISION/OTHER 11/09/2006 COMPLETED Review Details
11/09/2006 REVISION - - 1ST 11/09/2006 COMPLETED Review Details
11/17/2005 PLANS OK TO SUBMIT - SITE 11/17/2005 COMPLETED Review Details
11/17/2005 SITE 12/19/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM05786
Permit Status: C of o
Permit Description: TI:CHURCH
Total Outstanding Activity Conditions - 1
Date Name
11/17/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM05786
Permit Description: TI:CHURCH
Total Completed Inspections - 28
Date Description Inspector Results Comments
10/11/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
10/17/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
OK WALL COVER EAST AREAS

NOTE: EMERGENCY LIGHTING TO BE FED FROM LIGHTING IN AREA -- 700.12 PROVIDE BACK SUPPORT FOR RECEPTACLE BOXES SO THEY WON'T ROLL INTO WALL.
10/17/2006 FRAMING JBURGE Approved IVRS - Inspection :*
10/25/2006 SHEET ROCK NAILING AALEGRIA Approved IVRS - Inspection :*
PROVIDE FIRE-SEALANT ON ALL PENETRATIONS
ON FIRE WALL A-3/B CLASSIFICATION
11/13/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
YOU CANNOT HAVE COMBUSTIBLE MATERIAL IN A RETURN AIR PLENUM. ALL WOOD ABOVE RESTROOMS MUST BE COVERED. CHECKED CONDENSATE DRAIN LINES - OK TO INSULATE. RECALL FOR INSPECTION.
11/14/2006 PLUMBING - GAS PRESSURE TEST JMILITEL Approved IVRS - Inspection :*
7 PSI TEST IS OK
PROVIDE ACCESS TO ROOF.
CANNOT LEAVE CLEARANCE UNTIL EQUIPMENT ON ROOF HAS BEEN CHECKED.
11/14/2006 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
OK TO SET TILES THROUGHOUT
11/20/2006 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
1. RELOCATED FIXTURES TO BE EFFECTIVELY ATTACHED TO GRID.
2. INSTALL FLEX FOR 2-CORD CONNECTED FIXTURES.
3. FINISH #1 & #2 OF PREVIOUS INSPECTION.

OK TO TILE EXCEPT AS NOTED.
11/28/2006 MECHANICAL - FINAL LHANLY Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. COMBUSTIBLE MATERIAL IN RETURN AIR PLENUM
REFERENCE NOTES DATED 11/13/06
INSPECTION STOPPED
12/06/2006 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
COMBUSTIBLES HAVE BEEN COVERED WITH SCRIM
ON FINAL HAVE A LADDER SETUP TO ACCESS THE ROOF.
PROVIDE AIR BALANCE REPORT AS PER PLANS.
12/12/2006 FIRE - FINAL LTHOMAS Approved
12/12/2006 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
12/12/2006 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
12/12/2006 RIGHT OF WAY - FINAL PWHIDDON Approved TEMP ONLY (due to clear-up needed & to finish work.) PER EMAIL
12/13/2006 PLUMBING - FINAL RLEDONNE Approved IVRS - Inspection :*
1. PROVIDE GAS PRESS. TEST FOR FINAL GAS PRESSURE TEST
2. HAVE CONTRACTOR ON SITE FOR INSPECTION
12/13/2006 PLUMBING - GAS PRESS TEST FNL RLEDONNE Approved IVRS - Inspection :*
12/13/2006 PLUMBING - INTERMEDIATE RLEDONNE Approved IVRS - Inspection :*
01/30/2007 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
ENSURE THE INSTALLATION OF 1" SIGNAGE ON DOOR JAMBS @ MARKED EXITS -- DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED.
02/16/2007 LANDSCAPE - FINAL ACONNOR Approved
02/16/2007 ENGINEERING - FINAL JBRUCKME Approved
02/16/2007 OUTDOOR LIGHTING FINAL RHOLLAND Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - OUTDOOR LIGHTING RHOLLAND Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - PROGRESS RHOLLAND Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - TEMP POWER FOR TEST RHOLLAND Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - CONSTRUCTION POWER RHOLLAND Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - TEMPORARY SERVICE RHOLLAND Approved IVRS - Inspection :*
02/20/2007 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
COFO_001.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW
None SIGNS VIEW
5786-01-0001-01-REVISION001.TIF CONSTRPLANS VIEW
5786-01-0001-01-REVISION002.TIF CONSTRPLANS VIEW
5786-01-0001-01-REVISION2001.TIF CONSTRPLANS VIEW