Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/20/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. RELOCATED FIXTURES TO BE EFFECTIVELY ATTACHED TO GRID. 2. INSTALL FLEX FOR 2-CORD CONNECTED FIXTURES. 3. FINISH #1 & #2 OF PREVIOUS INSPECTION. OK TO TILE EXCEPT AS NOTED. |
|
| 11/13/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION ONLY 1. PROPERLY SUPPORT ALL LOW VOLTAGE WIRING OFF GRID 2. GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT EQUIPMENT - USE INDIVIDUAL SUPPORT WIRES AND SECURE AT BOTH ENDS. 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND SUPPORTED @ 4 1/2 FEET -- NOT LAYING ON GRID. 4. MAKE SURE EMERGENCY LIGHTING IS PER 2002 NEC 700.12 5. ALL FIXTURES TO HAVE SUPPORT WIRES (CHECK) 6. ROMEX NOT ALLOWED ABOVE CEILING DON'T INSTALL CEILING TILES BEFORE APPROVAL. |