Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EM LIGHTING ON AREA SERVED 700.12 2. NEED CITY STAMPS 3. FINISH ITEM #1 & 4 OF PREVIOUS INSPECTION |
|
| 01/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 (DRYWALL & TILE) ALSO LIGHT BOXES. 2. GROUND METAL BOXES 3. PLANS NOT REFLECTIVE OF LIGHTING NEW AND OLD 4. A/C LABELING NEED RENUMBERING - WE HAVE 2 OF EACH AT DIFFERENT LOCATIONS 5. PLANS DIFFER FROM INSTALLED BREAKERS IN DISTRIBUTION PANEL. ALSO, PLEASE VERIFY LOADS. 6. NURSERY LOCKED 7. PLEASE PROVIDE ACCESS TO ROOF AND ABOVE CEILING 8. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN SERVICE FOR INSPECTION. |