Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Apply Date:
04/14/2005
Applicant:
DAVID KINCAID
Description:
JACK IN BOX:NEW
Contractors:
  • PREMIER CONSTRUCTION CORPORATION
  • PREMIER RECONSTRUCTION SPECIALIST INC (FN)

Permit Reviews

Permit Number - T05CM01648
Permit Status: C of o
Permit Description: JACK IN BOX:NEW
Start Date Submittal Complete Date Status  
02/10/2006 3RD PARTY REVIEW-REVISION/OTHER 02/22/2006 COMPLETED Review Details
04/14/2005 PLANS OK TO SUBMIT - RES 3RD PARTY 04/20/2005 COMPLETED Review Details
04/20/2005 3RD PARTY REVIEW-COMMERCIAL 06/15/2005 COMPLETED Review Details
06/09/2006 3RD PARTY REVIEW-REVISION/OTHER 06/09/2006 COMPLETED Review Details
06/15/2005 POST 3RD PARTY REVIEW 07/01/2005 COMPLETED Review Details
08/23/2005 RESUBMITTAL 08/23/2005 COMPLETED Review Details
12/13/2005 3RD PARTY REVIEW-REVISION/OTHER 12/16/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM01648
Permit Status: C of o
Permit Description: JACK IN BOX:NEW
Total Outstanding Activity Conditions - 1
Date Name
04/14/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM01648
Permit Description: JACK IN BOX:NEW
Total Completed Inspections - 43
Date Description Inspector Results Comments
11/10/2005 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
EXCLUDES CANOPY AREA AND SITE WALLS
11/10/2005 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
11/14/2005 ELECTRIC - CONSTRUCTION POWER CCLEMENS Approved IVRS - Inspection :*
11/14/2005 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*FLOOR SINKS IN MONO POUR INSTALLED OK
ALL INTERIOR SINKS AND DRAINS ARE BLOCKED OUT.
WATER SERVICE UNDER SLAB OK
ROOF DRAINS UNDER SLAB OK- SUBJECT TO TEST AT A LATER DATE.
OK FOR CONCRETE.
NEED TO SEE INTERCEPTOR
11/15/2005 TEP CLEARANCE - AM JKOZUCH Approved TEMP CONST POWER
12/01/2005 FUEL PIPING INSP. & PRESS TEST RDRAVES Approved
12/09/2005 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
OK TO COVER REMAINDER - ELECTRICAL FUELING CONDUIT IN DITCH, BUILDING TO CANOPY
12/19/2005 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
1) EXCLUDES PARAPETS AND TOWER ROOF
12/21/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
1. DISCUSSED YARDWATER REQUIREMENTS W/SC
12/28/2005 SITE - SEWER RMYERS Approved IVRS - Inspection :*SOME OF THE PIPING BETWEEN BLDG AND INTERCEPTOR COVERD W/O INSPECTION.
INTERCEPTOR NOT VENTED PER PLAN
VENT SIZE MAY NOT BE REDUCED
VENT TO BE WITHIN 10' OFF INTERCEPTOR
USE DRAINAGE FITTINGS
INVERT OF VENT TO BE ABOVE DRAINAGE CENTERLINE
01/17/2006 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*SPLIT SYSTEM
BOTH SYSTEMS PRESSURE TEST OK
01/17/2006 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection :*
01/17/2006 FRAMING AQUIROZ Approved IVRS - Inspection :*
01/24/2006 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
01/26/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
04/06/2006 MECHANICAL - PROGRESS JMILITEL Approved IVRS - Inspection :*
FIRE WRAP NOT INSTALLED PER MANUFACTURERS SPECS.
PLEASE PROVIDE INSTALL INSTRUCTIONS.
EXTEND FIRE WRAP TO THE OUTLET TERMINAL.
PROVIDE 1" CLEARANCE FROM INSULATION & COMBUSTIBLES
AROUND WATER HEATER VENTS 1-60 DEGREE OFFSET ALLOWED.
HORIZONTAL SECTION CANNOT EXCEED 75% OF TOTAL HEIGHT.
DUCT SMOKE DETECTOR SENSING TUBES MUST COVER 85% OF PLENUM & BE AHEAD OF ALL DUCT CONNECTIONS.
04/07/2006 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
1. ABS DWV MAY NOT BE INSTALLED IN EXTERIOR EXPOSED LOCATION.
2. ANSUL VALVE ABOVE T-BAR MAY NOT USE UNION.
04/07/2006 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
05/08/2006 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection :*
05/10/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
1. GAS BOND & WATER BOND IN CEILING OK
2. J-BOX MISSING COVER ABOVE FRYERS - LEAVE OPEN
OK TO COVER LEAVE OPEN FOR NEXT INSPECTION.
05/10/2006 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
05/10/2006 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
05/14/2006 ELECTRIC - TEMPORARY SERVICE RHOLLAND Approved IVRS - Inspection :*
OK TEMP POWER FOR TEST
05/30/2006 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
05/30/2006 MECHANICAL - HOODS CWILLIAM Approved IVRS - Inspection :*
05/30/2006 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
06/02/2006 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
06/06/2006 FUEL TANK FINAL 791-4502 LLAKEY Approved
06/06/2006 FIRE - FINAL LLAKEY Approved
06/06/2006 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
06/08/2006 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :*
06/08/2006 ELECTRIC - PROGRESS CCLEMENS Approved IVRS - Inspection :*
06/08/2006 OUTDOOR LIGHTING FINAL CCLEMENS Approved IVRS - Inspection :*
06/09/2006 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL (NOTE: NO NEW WORK IN R.O.W.)
06/09/2006 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
06/09/2006 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
06/21/2006 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
1. ALL CORRECTIONS MADE OK
PLUMBING FINAL OK
OK FOR C OF O PENDING ANY OTHER INSPECTIONS.
10/27/2006 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
PARTIAL FOR TEMP C OF O
WILL RECALL FOR BUILDING FINAL & FINAL C OF O
10/27/2006 ENGINEERING - FINAL JFEMLING Approved The following items must be complete prior to final C of O.
1) Provide engineering cert. that basins and drainage ways have been constructed per the approved plans.
2) Clean all storm M.H.
3) Grout all storm M.H. frame and grate in place.
4) Complete sidewalk to ROW at SE corner of lot as shown on the approved grading plan.
5) Basin #1 is not constructed per plan, construct per plan or submit revision to city of review and approval.
6) Basin 3A not constructed. Construct per plan or submit revision to city of review and approval.
7) Storm M.H. in drive isle between basin 2 and 3B not found.
8) Repair erosion at concrete inlet to basin 2
9) Sidewalk not constructed between building and private drive as shown on approved grading plan.
10/27/2006 LANDSCAPE - FINAL ACONNOR Approved OK for Temp C of O

Complete ROW DG for approval or per ADOT instructions.
10/30/2006 ELECTRIC - UFER CCLEMENS Approved
11/01/2006 SIGN - FINAL JYBARRA Approved SIGNS COMPLETE; HOWEVER, ACCOUNT IN ARREARS FROM SEPT; MUST PAY REG FEES BEFORE C/O CAN BE ISSUED
03/05/2007 PERMIT FINALED BFLORES Approved