Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2006 | MECHANICAL - PROGRESS | Approved | IVRS - Inspection :* FIRE WRAP NOT INSTALLED PER MANUFACTURERS SPECS. PLEASE PROVIDE INSTALL INSTRUCTIONS. EXTEND FIRE WRAP TO THE OUTLET TERMINAL. PROVIDE 1" CLEARANCE FROM INSULATION & COMBUSTIBLES AROUND WATER HEATER VENTS 1-60 DEGREE OFFSET ALLOWED. HORIZONTAL SECTION CANNOT EXCEED 75% OF TOTAL HEIGHT. DUCT SMOKE DETECTOR SENSING TUBES MUST COVER 85% OF PLENUM & BE AHEAD OF ALL DUCT CONNECTIONS. |