Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
04/06/2006 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
FIRE WRAP NOT INSTALLED PER MANUFACTURERS SPECS.
PLEASE PROVIDE INSTALL INSTRUCTIONS.
EXTEND FIRE WRAP TO THE OUTLET TERMINAL.
PROVIDE 1" CLEARANCE FROM INSULATION & COMBUSTIBLES
AROUND WATER HEATER VENTS 1-60 DEGREE OFFSET ALLOWED.
HORIZONTAL SECTION CANNOT EXCEED 75% OF TOTAL HEIGHT.
DUCT SMOKE DETECTOR SENSING TUBES MUST COVER 85% OF PLENUM & BE AHEAD OF ALL DUCT CONNECTIONS.