Permit: T05CM01648

Parcel: 10120040D

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
05/30/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
01/17/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*CHECKED SUPPLY & EXHAUST IN RESTROOMS.
OK TO SHEET ROCK. CHECKED CONDENSATE DRAINS. INSULATE AS PER PLANS.
PLANS WERE APPROVED IN ERROR. ALL SUPPLY & RETURN DUCTS MUST BE INSULATED WITH MIN. R5 INSULATION INSIDE THE BLDG & R8 OUTSIDE THE BLDG. R4.2 INSULATION WILL NOT BE ACCEPTED.