Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/17/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*CHECKED SUPPLY & EXHAUST IN RESTROOMS. OK TO SHEET ROCK. CHECKED CONDENSATE DRAINS. INSULATE AS PER PLANS. PLANS WERE APPROVED IN ERROR. ALL SUPPLY & RETURN DUCTS MUST BE INSULATED WITH MIN. R5 INSULATION INSIDE THE BLDG & R8 OUTSIDE THE BLDG. R4.2 INSULATION WILL NOT BE ACCEPTED. |