Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address:
2828 N STONE AV
Address NEW:
2828 N STONE AV
Apply Date:
11/17/2004
Applicant:
SWAN WAYNE E
Description:
TI:OFFICE
Architects:
  • SWAN WAYNE E
Contractors:
  • G AND J DEVELOPMENT INC ,

Permit Reviews

Permit Number - T04CM05049
Permit Status: Final
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
11/17/2004 COMMERCIAL TI 11/22/2004 COMPLETED Review Details
11/22/2004 REVISION 12/06/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM05049
Permit Status: Final
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
11/17/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T04CM05049
Permit Description: TI:OFFICE
Total Completed Inspections - 15
Date Description Inspector Results Comments
12/21/2004 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection :DENIED-ALL PATIENT CARE ROOMS MUST COMPLY WITH SECTION 517 OF THE NATIONAL ELECTRICAL CODE. THE MC CABLE MUST BE HCF GRADE, WITH APPROVED CONNECTORS TO TERMINATE IN BOXES. ALL OUTLETS- POWER AND LIGHTING MUST BE WIRED WITH HCF MC. CORRECT AND RECALL.
12/21/2004 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection :ALL PATIENT CARE ROOMS MUST COMPLY WITH SECTION 517 OF THE NATIONAL ELECTRICAL CODE. THE MC CABLE MUST BE HCF GRADE, WITH APPROVED CONNECTORS TO TERMINATE IN BOXES. ALL OUTLETS-POWER AND LIGHTING MUST BE WIRED WITH HCF MC. CORRECT AND RECALL.
The wiring is not complete or does not comply with code.| 245*
12/21/2004 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
12/28/2004 FRAMING HLEYVA Approved IVRS - Inspection :*
12/29/2004 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*/OK TO COVER ALL AREAS
12/29/2004 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*/1)NOT INSTALLED PER PLAN. NO REDLINES ON SITE 2)EXCEPT WYE BRANCH OR END OF THE LINE CLEAN-OUT, CLEAN-OUTS SHALL BE INSTALLED ABOVE THE FLOW LINE OF THE DRAIN 3) ALL OVER HEAD PIPING TO BE INSTALLED TO TABLE 3-19 94UPC AND INSTALLATION STANDARD 4)HOT PIPING INSULATED BEFORE INSPECTION 5)CONTRACTOR TO BED, AND SHADE ABS BELOW GRADE WITH CLEAN-FILL
12/29/2004 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
12/29/2004 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
01/27/2005 SHEET ROCK NAILING HLEYVA Approved IVRS - Inspection :* APPROVED
02/28/2005 FIRE - FINAL LTHOMAS Approved
03/14/2005 ELECTRIC - FINAL RMAJUTA Approved
03/15/2005 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :* BACKFLOW PROTECTION ADDED AT IRRIGATION/ PUMP LOCATION. PLUMBING FINAL OK. OK FOR C OF O PENDING ANY OTHER INSPECTION.
03/16/2005 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :* OK C OF O
03/23/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :* APPROVED
10/12/2005 PERMIT FINALED LJACKSON Approved