Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/05/2005 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :*APPROVED |
| 12/21/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection :DENIED-ALL PATIENT CARE ROOMS MUST COMPLY WITH SECTION 517 OF THE NATIONAL ELECTRICAL CODE. THE MC CABLE MUST BE HCF GRADE, WITH APPROVED CONNECTORS TO TERMINATE IN BOXES. ALL OUTLETS- POWER AND LIGHTING MUST BE WIRED WITH HCF MC. CORRECT AND RECALL. |