Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* BACKFLOW PROTECTION ADDED AT IRRIGATION/ PUMP LOCATION. PLUMBING FINAL OK. OK FOR C OF O PENDING ANY OTHER INSPECTION. | |
| 03/11/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/10/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WATER LINE RUN TO FOUNTAIN NOT PROTECTED. IRRIGATION CONNECTION NOT PROTECTED 2) SINKS ADDED INSIDE-OK 3) PLUMBING FINAL WILL BE ISSUED WHEN BACKFLOW/SIPHOAGE ISSUE IS RESOLVED |
|
| 03/09/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BACKFLOW DEVICE FREE FROM STUCCO, HOWEVER IF THE RPPBP DISCHARGES IT WILL OR MAY DAMAGE THE WALL. 2) HOSE BIBB WITH NO VACUUM BREAKER CONNECTED TO FOUNTAIN PUMP-AND IRRIGATION CONNECTED TO BIBB. 3) ALL SINKS REQUIRED REQUIRE CLEAN-OUT | |
| 02/28/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BACKFLOW DEVICE ENCASED IN STUCCO 1) NOT ACCESSIBLE FOR REPAIR/REPLACEMENT 2) MAY NOT BE DIRECTLY EMBEDDED |