Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/12/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*APPROVED
01/07/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The fixtures are not per plans and specifications.| 250*
THE CLIPS ON THE FIXTURES MUST FULLY ENGAGE THE TEE GRID.YOUR INSTALLATION DOES NOT MEET THIS REQUIREMENT.YOU MAY SCREW THE FIXTURE AND GRID TO MEET THE NEC ART.300,et al? USE PAN HEAD SELF TAPPING SCREWS - ONE,CENTER, AT EACH END. CORRECT & RECALL. THANKS.
12/21/2004 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :ALL PATIENT CARE ROOMS MUST COMPLY WITH SECTION 517 OF THE NATIONAL ELECTRICAL CODE. THE MC CABLE MUST BE HCF GRADE, WITH APPROVED CONNECTORS TO TERMINATE IN BOXES. ALL OUTLETS-POWER AND LIGHTING MUST BE WIRED WITH HCF MC. CORRECT AND RECALL.
The wiring is not complete or does not comply with code.| 245*