Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address:
555 N PANTANO RD
Apply Date:
07/15/2004
Applicant:
ERIC GRIGEL
Description:
REMODEL:CLUB HOUSE
Architects:
  • HANSON GROUP , THE
Contractors:
  • CANYON BUILDING AND DESIGN L L C

Permit Reviews

Permit Number - T04CM03267
Permit Status: Final
Permit Description: REMODEL:CLUB HOUSE
Start Date Submittal Complete Date Status  
01/27/2005 REVISION - WALK THRU 01/27/2005 COMPLETED Review Details
07/15/2004 COMMERCIAL TI 07/29/2004 COMPLETED Review Details
07/22/2004 COMMERCIAL TI 08/03/2004 COMPLETED Review Details
08/03/2004 OTHER 09/10/2004 COMPLETED Review Details
12/15/2004 REVISION - WALK THRU 12/15/2004 COMPLETED Review Details
12/21/2004 REVISION 12/21/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM03267
Permit Status: Final
Permit Description: REMODEL:CLUB HOUSE
Total Outstanding Activity Conditions - 1
Date Name
07/15/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T04CM03267
Permit Description: REMODEL:CLUB HOUSE
Total Completed Inspections - 22
Date Description Inspector Results Comments
10/12/2004 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*/WATER TEST WASTE & VENT AND GREASE WASTE THRU ROOF OK. 1)PROVIDE REVISED CITY APPROVED PLAN OF ADDITION OF HAND SINK WASTE & VENT PER YOUR RED LINE DRAWING.
10/15/2004 FRAMING LHANLY Approved IVRS - Inspection :NOTCH OUT KINGSTUD TO RELOCATE ROMEX BETWEEN KINGSTUD AND TRIMMER
OK TO COVER WHEN ELEC INSP APPROVES INTERMEDIATE
10/27/2004 PLUMBING - INTERMEDIATE JSTANLEY Approved IVRS - Inspection :*/PARTIAL IN KITCHEN AREA ONLY TEST ON WATER ONLY AT THIS TIME. NO REVISEDPLAN ON JOB AS PER LAST REQUEST. PLEASE PROVIDE REVISED PLAN BY NEXT INSP. IF YOU COVER YOU COVER AT YOUR OWN RISK
10/29/2004 SHEET ROCK NAILING RSUBA Approved IVRS - Inspection :*
11/16/2004 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*/I INSPECTED GREASE DUCT - OK TO FIRE WRAP. BE SURE TO MAINTAIN 3" OVERLAPS & BANDS WITHIN 1 1/2" FROM EDGE OF WRAP & 10 1/2" ON CENTER.
11/16/2004 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
11/16/2004 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :* OK TO CLEAR METER
11/17/2004 TEP CLEARANCE - AM JKOZUCH Approved INC
11/22/2004 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
11/22/2004 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
11/24/2004 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :* SPLIT BOLT LISTED FOR RUN & TAP ONLY-USED APPVD. MULTI TAP. IDENTIFY GROUNDING ELECTRODE CONDUCTOR @ MULTI TAP. SUPPORT GROUND & FLEX @ TRANSFORMER. OK KITCHEN CEILING.
11/26/2004 FIRE - FINAL LLAKEY Approved
11/26/2004 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
12/14/2004 MECHANICAL - FINAL JMILITEL Approved 1) EXHAUST FAN NOT PER PLANS. EQUIPMENT SCHEDULE CALLS FOR 1 1/2 H. P MOTOR . FANIS 1 H.P. 2) MAKE UP AIR UNIT MUST BE INTERLOCKED WITH EXHAUST FAN. SEE NOTE ON MAKE UP AIR SCHEDULE & EXHAUST FAN SCHEDULE. 3) PROVIDE A SUN SHIELD OVER CANVAS CONNECTOR ON MAU. RECALL FOR INSPECTION.
12/14/2004 PLUMBING - FINAL JSTANLEY Approved IVRS - Inspection :*NOT READY. PLEASE PROVIDE AN APPROVED REVISION. PLEASE PROVIDE PROPER STAMPS ON REVISION CAL IN ALL REQUIRED INSPECTION. BEFORE FINAL IS GIVEN.
12/14/2004 BUILDING - FINAL HLEYVA Approved IVRS - Inspection :*
1) ALL TRADES TO BE APPROVED PRIOR TO BLDG
12/20/2004 PLUMBING - GAS PRESSURE TEST JSTANLEY Approved IVRS - Inspection :*/SEE REVISED PLAN P-1 & APPROVED 12/15/04. PLEASE INSTALL AS PER APPROVED PLAN. PLAN CALLS FOR 1 1/4 AND 3/4" HAS BEEN INSTALLED
01/27/2005 ELECTRIC - FINAL RSUBA Approved IVRS - Inspection :*
02/02/2005 PLUMBING - PROGRESS JSTANLEY Approved IVRS - Inspection :*
02/04/2005 MECHANICAL - INTERMEDIATE JMILITEL Approved
02/04/2005 PERMIT FINALED RSUBA Approved
02/04/2005 BUILDING ABOVE CEILING BSTEVENS Approved

Documents

File Name Document Type  
None LETTER OF COMPLETION VIEW
None DOCUMENTS VIEW