Permit: T04CM03267
Permit Details
Apply Date:
07/15/2004
Applicant:
ERIC GRIGEL
Description:
REMODEL:CLUB HOUSE
Architects:
- HANSON GROUP , THE
Contractors:
- CANYON BUILDING AND DESIGN L L C
Permit Reviews
Permit Number - T04CM03267
Permit Status: Final
Permit Description: REMODEL:CLUB HOUSE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/27/2005 | REVISION - WALK THRU | 01/27/2005 | COMPLETED |
07/15/2004 | COMMERCIAL TI | 07/29/2004 | COMPLETED |
07/22/2004 | COMMERCIAL TI | 08/03/2004 | COMPLETED |
08/03/2004 | OTHER | 09/10/2004 | COMPLETED |
12/15/2004 | REVISION - WALK THRU | 12/15/2004 | COMPLETED |
12/21/2004 | REVISION | 12/21/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM03267
Permit Status: Final
Permit Description: REMODEL:CLUB HOUSE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/15/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04CM03267
Permit Description: REMODEL:CLUB HOUSE
Total Completed Inspections - 22
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2004 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection :*/WATER TEST WASTE & VENT AND GREASE WASTE THRU ROOF OK. 1)PROVIDE REVISED CITY APPROVED PLAN OF ADDITION OF HAND SINK WASTE & VENT PER YOUR RED LINE DRAWING. |
10/15/2004 | FRAMING | LHANLY | Approved | IVRS - Inspection :NOTCH OUT KINGSTUD TO RELOCATE ROMEX BETWEEN KINGSTUD AND TRIMMER OK TO COVER WHEN ELEC INSP APPROVES INTERMEDIATE |
10/27/2004 | PLUMBING - INTERMEDIATE | JSTANLEY | Approved | IVRS - Inspection :*/PARTIAL IN KITCHEN AREA ONLY TEST ON WATER ONLY AT THIS TIME. NO REVISEDPLAN ON JOB AS PER LAST REQUEST. PLEASE PROVIDE REVISED PLAN BY NEXT INSP. IF YOU COVER YOU COVER AT YOUR OWN RISK |
10/29/2004 | SHEET ROCK NAILING | RSUBA | Approved | IVRS - Inspection :* |
11/16/2004 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :*/I INSPECTED GREASE DUCT - OK TO FIRE WRAP. BE SURE TO MAINTAIN 3" OVERLAPS & BANDS WITHIN 1 1/2" FROM EDGE OF WRAP & 10 1/2" ON CENTER. |
11/16/2004 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
11/16/2004 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection :* OK TO CLEAR METER |
11/17/2004 | TEP CLEARANCE - AM | JKOZUCH | Approved | INC |
11/22/2004 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* |
11/22/2004 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
11/24/2004 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* SPLIT BOLT LISTED FOR RUN & TAP ONLY-USED APPVD. MULTI TAP. IDENTIFY GROUNDING ELECTRODE CONDUCTOR @ MULTI TAP. SUPPORT GROUND & FLEX @ TRANSFORMER. OK KITCHEN CEILING. |
11/26/2004 | FIRE - FINAL | LLAKEY | Approved | |
11/26/2004 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | |
12/14/2004 | MECHANICAL - FINAL | JMILITEL | Approved | 1) EXHAUST FAN NOT PER PLANS. EQUIPMENT SCHEDULE CALLS FOR 1 1/2 H. P MOTOR . FANIS 1 H.P. 2) MAKE UP AIR UNIT MUST BE INTERLOCKED WITH EXHAUST FAN. SEE NOTE ON MAKE UP AIR SCHEDULE & EXHAUST FAN SCHEDULE. 3) PROVIDE A SUN SHIELD OVER CANVAS CONNECTOR ON MAU. RECALL FOR INSPECTION. |
12/14/2004 | PLUMBING - FINAL | JSTANLEY | Approved | IVRS - Inspection :*NOT READY. PLEASE PROVIDE AN APPROVED REVISION. PLEASE PROVIDE PROPER STAMPS ON REVISION CAL IN ALL REQUIRED INSPECTION. BEFORE FINAL IS GIVEN. |
12/14/2004 | BUILDING - FINAL | HLEYVA | Approved | IVRS - Inspection :* 1) ALL TRADES TO BE APPROVED PRIOR TO BLDG |
12/20/2004 | PLUMBING - GAS PRESSURE TEST | JSTANLEY | Approved | IVRS - Inspection :*/SEE REVISED PLAN P-1 & APPROVED 12/15/04. PLEASE INSTALL AS PER APPROVED PLAN. PLAN CALLS FOR 1 1/4 AND 3/4" HAS BEEN INSTALLED |
01/27/2005 | ELECTRIC - FINAL | RSUBA | Approved | IVRS - Inspection :* |
02/02/2005 | PLUMBING - PROGRESS | JSTANLEY | Approved | IVRS - Inspection :* |
02/04/2005 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
02/04/2005 | PERMIT FINALED | RSUBA | Approved | |
02/04/2005 | BUILDING ABOVE CEILING | BSTEVENS | Approved |