Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2005 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 11/24/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* SPLIT BOLT LISTED FOR RUN & TAP ONLY-USED APPVD. MULTI TAP. IDENTIFY GROUNDING ELECTRODE CONDUCTOR @ MULTI TAP. SUPPORT GROUND & FLEX @ TRANSFORMER. OK KITCHEN CEILING. |
| 11/22/2004 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 11/16/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |