Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2004 JIM EGAN FIRE REVIEW Approved
07/16/2004 DAN CASTRO ZONING REVIEW Approved
07/16/2004 JIM TATE ENGINEERING REVIEW Approved
07/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide listing information for the fire wrap for the grease duct.
2. Provide the installed weight of the hood with support calculations and show how the hood is mounted to the structure. Reference Section 507.6, IMC 2000.
3. Revise the hood exhaust rate to comply with Section 507.13.3, IMC 2000.
07/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/22/2004 ROBERT SHERRY WATER REVIEW Approved
07/29/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
07/29/2004 EGRANT1 WWM REVIEW Needs Review