Permit: T04CM03267

Parcel: 133400020


Addresses:

555 N PANTANO RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T04CM03267

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
02/04/2005 ELECTRIC - SERVICE UPGRADE Approved
11/16/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :* OK TO CLEAR METER
11/12/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NEED NEUTRAL DISCONNECT LINK AT 100 AMP
2) NEED NEUTRAL TO EACH SERVICE
3) NEED GROUND BUSHING AND BOND JUMPER AT ALL RACEWAY
4) BOND TO GUTTER
5) WHERE ARE SERVICE REJECTION PINS
6) USE APPROVED SIZED LUGS FOR CONDUCTORS
7) NO STACKING OF LUGS
8) TIGHTEN LOOSE FITTINGS TO TRANSFORMER
9) VERIFY IF TRANSFORMER ? CLEARANCE TO COMBUSTIBLES
10) FINISH PREVIOUS ITEMS
11/11/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MAIN BOND JUMPER FOR 2 CONDUITS AT C.T. TO BE MINIMUM OF #2 AWG CU.
2) INSTALL NEUTRAL DISCONNECT AS REQUIRED IN LISTING
3) NO LUG STACKING
4) TRANSFORMER NOT READY-CONDUIT STRAPING, GROUNDING AND TERMINATION
5) SUB PANEL IMPROPERLY WIRED AND CALLS FOR NEW
6) COMPLETE ALL
11/10/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NEED NEUTRAL DISCONNECT LINK AT 100 AMP
2) NEED NEUTRAL TO SEACH SERVICE
3) NEED GROUND BUSH. AND BOND JUMPER AT ALL RACEWAYS
4) BOND TO GUTTER