Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T04CM03267
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/04/2005 | ELECTRIC - SERVICE UPGRADE | Approved | ||
11/16/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* OK TO CLEAR METER | |
11/12/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NEED NEUTRAL DISCONNECT LINK AT 100 AMP 2) NEED NEUTRAL TO EACH SERVICE 3) NEED GROUND BUSHING AND BOND JUMPER AT ALL RACEWAY 4) BOND TO GUTTER 5) WHERE ARE SERVICE REJECTION PINS 6) USE APPROVED SIZED LUGS FOR CONDUCTORS 7) NO STACKING OF LUGS 8) TIGHTEN LOOSE FITTINGS TO TRANSFORMER 9) VERIFY IF TRANSFORMER ? CLEARANCE TO COMBUSTIBLES 10) FINISH PREVIOUS ITEMS |
|
11/11/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MAIN BOND JUMPER FOR 2 CONDUITS AT C.T. TO BE MINIMUM OF #2 AWG CU. 2) INSTALL NEUTRAL DISCONNECT AS REQUIRED IN LISTING 3) NO LUG STACKING 4) TRANSFORMER NOT READY-CONDUIT STRAPING, GROUNDING AND TERMINATION 5) SUB PANEL IMPROPERLY WIRED AND CALLS FOR NEW 6) COMPLETE ALL |
|
11/10/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NEED NEUTRAL DISCONNECT LINK AT 100 AMP 2) NEED NEUTRAL TO SEACH SERVICE 3) NEED GROUND BUSH. AND BOND JUMPER AT ALL RACEWAYS 4) BOND TO GUTTER |