Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2005 |
MECHANICAL - HOODS |
|
Approved |
|
| 11/16/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :*/I INSPECTED GREASE DUCT - OK TO FIRE WRAP. BE SURE TO MAINTAIN 3" OVERLAPS & BANDS WITHIN 1 1/2" FROM EDGE OF WRAP & 10 1/2" ON CENTER. |
| 09/30/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :* |