Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address:
2484 E RIVER RD
Address NEW:
2484 E RIVER RD
Apply Date:
03/26/2003
Applicant:
METRO PERMIT EXPRESS
Description:
LABORATORY:NEW
Architects:
  • EGLIN, EVAN SAR
Contractors:
  • EPSTEIN FENTON L L C ,

Permit Reviews

Permit Number - T03CM01511
Permit Status: C of o
Permit Description: LABORATORY:NEW
Start Date Submittal Complete Date Status  
03/26/2003 PLANS OK TO SUBMIT - 3RD PARTY 04/03/2003 COMPLETED Review Details
03/26/2003 PLANS OK TO SUBMIT - SITE 03/26/2003 COMPLETED Review Details
03/27/2003 SITE 04/28/2003 COMPLETED Review Details
04/04/2003 3RD PARTY REVIEW-COMMERCIAL 04/18/2003 COMPLETED Review Details
05/16/2003 RESUBMITTAL - SITE 06/12/2003 COMPLETED Review Details
05/19/2003 3RD PARTY REVIEW-COMMERCIAL 06/16/2003 COMPLETED Review Details
05/21/2004 3RD PARTY REVIEW-REVISION/OTHER 05/26/2004 COMPLETED Review Details
06/20/2003 RESUBMITTAL 03/04/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM01511
Permit Status: C of o
Permit Description: LABORATORY:NEW
Total Outstanding Activity Conditions - 1
Date Name
03/26/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM01511
Permit Description: LABORATORY:NEW
Total Completed Inspections - 39
Date Description Inspector Results Comments
04/28/2004 ELECTRIC - UFER MCAPISTR Approved IVRS - Inspection :*
05/06/2004 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
05/18/2004 PLUMBING - SEWER HCS CONNECT JSTANLEY Approved IVRS - Inspection :*
05/18/2004 PLUMBING - YARD WTR LINE/TEST JSTANLEY Approved IVRS - Inspection :*/ TEST OK ON UNDERGROUND SOIL. YARDWTR OK. HCS OK. PLEASE PROVIDE LETTER ON USE OF PVC.
05/18/2004 PLUMBING - ROUGH, SOIL JSTANLEY Approved IVRS - Inspection :*
05/28/2004 BUILDING PRE-SLAB RSUBA Approved IVRS - Inspection :*
07/22/2004 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection :*
07/28/2004 ELECTRIC - UNDERGROUND MCAPISTR Approved IVRS - Inspection :*/ 1) PVC FOR POWER AND TEL. OK OT COVER. WHAT IS TO BE DONE ABOUT THE EMERGENCY POWER SYSTEM?
08/05/2004 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
08/05/2004 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection :*
09/03/2004 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
09/03/2004 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
09/10/2004 FRAMING AMATHIES Approved IVRS - Inspection :*/ 1) INTERIOR METAL FRAME OK
09/13/2004 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*/SUSPENDED ROUGH DUE TO ONLY
09/14/2004 STUCCO MESH HLEYVA Approved IVRS - Inspection :*
09/15/2004 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
09/23/2004 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
09/28/2004 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
10/01/2004 PLUMBING - GAS PRESSURE TEST JSTANLEY Approved IVRS - Inspection :*
10/01/2004 PLUMBING - ROOF DRAINS JSTANLEY Approved IVRS - Inspection :*
10/26/2004 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*/OK FOR CEILING TILES. LEAVE OUT A TILE UNDER EACH SMOKE DETECTOR.
10/26/2004 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection :*
10/26/2004 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection :*
10/26/2004 U VALUE FOR WINDOW LHANLY Approved IVRS - Inspection :*
10/26/2004 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection :*
11/03/2004 ELECTRIC - TEMP POWER FOR TEST MCAPISTR Approved IVRS - Inspection :* OK TO CLEAR
11/16/2004 TEP CLEARANCE - AM JKOZUCH Approved BOND POSTED
12/08/2004 PLUMBING - FINAL JSTANLEY Approved IVRS - Inspection :*/FINAL OK STOI. LAST INSP ON JOB PLEASE PROVIDE GAS CARD
12/14/2004 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection :
The fixtures are not per plans and specifications.| 250*/1)NITE LITE IN LAB NOT FITTED W/EMERGENCY BATT. PAK. 2)ARE EXIT SIGNS REQUIRED TO HAVE EMERGENCY BATT. PAK? PROVIDE LETTER FROM ENGINEER OF RECORD CLARIFYING THIS 3)CLOSETS CONTAINING ELECTRICALLY OPERATED EQUIPMENT (WATER HTR) MUST HAVE A LIGHT FIXTURE. 4)EXTERIOR LIGHT FIXTURES NOT INSTALLED. I NEED TO SEE THEM TO DETERMINE IF THEY ARE IN COMPLIANCE WITH OUTDOOR LIGHTING ORDINANCE. CORRECT AND RECALL
12/17/2004 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*/IMC 306.5. ACCESS, LOWER ROOF TO UPPER ROOF, (UNITS ON EACH LEVEL) IN EXCESS OF 30", REQUIRES PERMANENT MEANS, TO ACCESS EQUIP. HAVE ARCH. PROVIDE DIRECTION.
12/22/2004 FIRE - FINAL LTHOMAS Approved
01/03/2005 OUTDOOR LIGHTING FINAL MCAPISTR Approved IVRS - Inspection :*
01/05/2005 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
01/07/2005 RIGHT OF WAY - FINAL MOTERO Approved CLEAR
12/29/2008 ENGINEERING - FINAL JFEMLING Approved Approved
04/07/2009 NPPO - FINAL ACONNOR Approved
04/07/2009 LANDSCAPE - FINAL ACONNOR Approved
04/07/2009 BUILDING - FINAL AQUIROZ Approved CLEARED BY PHONE
04/13/2009 PERMIT FINALED BGRANT Approved