Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/04/2005 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* SORRY FOR APPEARANCE OF PERM ??? |
| 12/17/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/IMC 306.5. ACCESS, LOWER ROOF TO UPPER ROOF, (UNITS ON EACH LEVEL) IN EXCESS OF 30", REQUIRES PERMANENT MEANS, TO ACCESS EQUIP. HAVE ARCH. PROVIDE DIRECTION. |
| 12/10/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/NEED ROOF ACCESS FOR FINAL. IF LOWEST PT. OF ACCESS EXCEEDS 16' MAX. PERM. ACCESS MAYBE NECESSARY |