Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01511
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/04/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) THE OMISSION OF PANEL B MUST BE APPROVED BY ENGINEER AND DOCUMENTED ON HIS LETTER 2) THE PANEL SCHEDULE ON PLAN MUST MATCH THE PANEL DIRECTORY 3) THE LOCK ON DEVICE FOR SPRINKLER MUST BE INSTALLED |
|
01/03/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*NITE LITE ( NL) NOT INSTALLED. THANKS | |
12/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250*/1)NITE LITE IN LAB NOT FITTED W/EMERGENCY BATT. PAK. 2)ARE EXIT SIGNS REQUIRED TO HAVE EMERGENCY BATT. PAK? PROVIDE LETTER FROM ENGINEER OF RECORD CLARIFYING THIS 3)CLOSETS CONTAINING ELECTRICALLY OPERATED EQUIPMENT (WATER HTR) MUST HAVE A LIGHT FIXTURE. 4)EXTERIOR LIGHT FIXTURES NOT INSTALLED. I NEED TO SEE THEM TO DETERMINE IF THEY ARE IN COMPLIANCE WITH OUTDOOR LIGHTING ORDINANCE. CORRECT AND RECALL |