Permit: T02CM05550
Permit Details
Apply Date:
12/03/2002
Applicant:
N/A
Description:
ADD:MULTIPURPOSE ROOM
Contractors:
- ARIZONA SCHOOL FACILITIES BOARD*T
- PACIFIC BUILDING INTERIORS INC ,
Permit Reviews
Permit Number - T02CM05550
Permit Status: C of o
Permit Description: ADD:MULTIPURPOSE ROOM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/12/2005 | REVISION | 01/12/2005 | COMPLETED |
| 04/10/2003 | RESUBMITTAL | 05/07/2003 | COMPLETED |
| 06/06/2003 | RESUBMITTAL | 06/25/2003 | COMPLETED |
| 12/03/2002 | COMMERCIAL TI | 03/27/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02CM05550
Permit Status: C of o
Permit Description: ADD:MULTIPURPOSE ROOM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/03/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T02CM05550
Permit Description: ADD:MULTIPURPOSE ROOM
Total Completed Inspections - 37
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2003 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection 0000*/ 1) WASTE AND VENT SOIL UNDERGROUND WATER TEST ONLY OK. 2) HCS CONNECTION IS OK. 3) PLEASE CALL BACK FOR PIPE WRAP IN CONCRETE AND TRAP PRIMER LINES PRIOP TO CONCRETE POUR. 4) PLEASE PROVIDE UPDATED CITY APPROVED DRAWING FOR UNDERGROUND WASTE AND VENT CHANGES TO PLAN. |
| 10/28/2003 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection 0000*/ 2" TYPE K-H2O SERVICE STUBBED OUT OF PAD - 50 PSI TEST OK. CONTRACTOR TO WRAP ALL PIPING IN CONCRETE PRIOR TO POUR. |
| 11/05/2003 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection 0000* UFER SHOULD BE IN BOTTOM 1/3 OF FOOTING. (2/0 ? 20' LONG CLAMPED TO CANT REBAR |
| 02/18/2004 | FRAMING | LHANLY | Approved | IVRS - Inspection 0000* |
| 02/18/2004 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection 0000* |
| 03/16/2004 | SHEET ROCK NAILING | LHANLY | Approved | IVRS - Inspection 0000* |
| 03/29/2004 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection 0000* |
| 03/29/2004 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection 0000* |
| 03/29/2004 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000* |
| 03/30/2004 | BUILDING - PROGRESS | RSUBA | Approved | IVRS - Inspection 0000* |
| 03/30/2004 | U VALUE FOR WINDOW | RSUBA | Approved | IVRS - Inspection 0000* |
| 03/31/2004 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 04/05/2004 | PLUMBING - ROOF DRAINS | RRICH | Approved | IVRS - Inspection 0000* |
| 04/05/2004 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection 0000*/ 5 PSI AIR TEST ON EASTERN RAIN DRAIN OK. |
| 04/22/2004 | PLUMBING - GAS PRESS TEST FNL | RRICH | Approved | IVRS - Inspection :*/ 1ΒΌ FROM SOUTHWEST CORNER EXTERIOR TO 3 ROOFTOP UNITS TO APPLIANCE VALVE 15 PSI AIR TEST OK. |
| 06/21/2004 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :*/ 1) CORRECTIONS MADE |
| 12/01/2004 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :*/ 1) CONCRETE OVER DRIVE WAY OK |
| 12/02/2004 | BUILDING ABOVE CEILING | LHANLY | Approved | IVRS - Inspection :* |
| 12/02/2004 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | IVRS - Inspection :* |
| 12/02/2004 | BUILDING PRE-SLAB | LHANLY | Approved | IVRS - Inspection :* |
| 12/02/2004 | STEM WALL/RETAINING WALL | LHANLY | Approved | IVRS - Inspection :* |
| 12/02/2004 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* |
| 12/02/2004 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* |
| 12/08/2004 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 12/08/2004 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 12/08/2004 | SIGN - FINAL | JSONKIN | Approved | IVRS - Inspection :* |
| 12/16/2004 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :*/FIRE DEPT. WILL CHECK DUCT SMOKE DETECTORS. OK FOR FINAL C/O |
| 12/17/2004 | ELECTRIC - FINAL | RMAJUTA | Approved | 1) MULTIPURPOSE ROOM APPROVED 2) NO RECORD OF NEW 200 AMP SW GEAR BEING INSOPECTED-NO RECORD OF CLEARANCE GROUNDING TO BE UNCOVERED, LETTER ON TORQUE OF SW GEAR AS PER MANUFACTURERS REQUIREMENTS 3) SEVERAL SHEETS OF ELECTRICAL PLANS MISSING 4) WILL NEED TO SEE GROUNDING ON SERVICE INCLUDING GAS AND WATER BOND 5) LETTER ON TORQUE FOR SWITCH GEAR OPEN SERVICE FOR INSPECTION |
| 12/17/2004 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | |
| 12/17/2004 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | |
| 01/24/2005 | ENGINEERING - FINAL | JBRUCKME | Approved | |
| 01/26/2005 | RIGHT OF WAY - FINAL | DLEE | Approved | |
| 02/02/2005 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 02/04/2005 | FIRE - FINAL | LTHOMAS | Approved | |
| 02/04/2005 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
| 02/07/2005 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection :* |
| 02/17/2005 | PERMIT FINALED | TACHONG | Approved |