Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/18/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/05/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* 1) ENG HAS SPECIFIED THAT YOU MUST BLOCK ALL EDGES OF SHEAR WALL. 2) ALL EXTERIOR WALLS ARE SHEASR WALL. 3) REMOVE TOP ROW OF SHEATHING, INSTALL BLOCKING OR STRAPS FOR WEST WALL AND UNBLOCKED RETURNS ON N & S WALL. 4)LEDGERS TO BE FASTENED 6"OC HORIZONTALLY PER PLAN. |
| 01/20/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* EXTERIOR WALLS. 1) FINISH NAILING SHEAR WALLS PER SCHEDULE(REF 6, 7, 8/252.1) 2) PROVIDE METAL MFR INFO FOR HORIZ WALL REINFROCEMENT( REF6/252.1) 3) ARE SHEASR WALLS BLOCKED OR UNBLOCKED- CURRENTLY UN-BLOCKED. 4) RFI FOSR CLAIRIFICATION OF NOTE FOR SCREWS @ 6" O.C. |