Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2004 |
PLUMBING - PROGRESS |
|
Approved |
IVRS - Inspection :*/ 1) CORRECTIONS MADE |
| 03/30/2004 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*/ SUPPORT ½ HOT AND COLD ON EXTERIOR OF EAST RESTROOM FOR LAV. / AIR OR WTR TEST EAST ROOF DRAIN. / 2" PVC SCH 40 TIED INTO 2" COPPER STUB AT BLD OVER TO RISER AT BACKFLOW PROTECTION. 50 PSI TEST PARTIAL APPROVAL PENDING SEEING CITY APPROVED DRAWING SHOWING ROUTE AND SIZING AND TERMINATION OF PIPING ON INLET END. |