Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
2255 N WYATT DR
Address NEW:
2255 N WYATT DR
Apply Date:
07/09/2002
Applicant:
N/A
Description:
TI:MEDICAL OFFICE/ADDITION
Architects:
  • MASCIA, FRANK
Contractors:
  • B F L CONSTRUCTION CO INC ,

Permit Reviews

Permit Number - T02CM03236
Permit Status: C of o
Permit Description: TI:MEDICAL OFFICE/ADDITION
Start Date Submittal Complete Date Status  
07/09/2002 SITE 07/31/2002 COMPLETED Review Details
07/09/2002 3RD PARTY REVIEW-COMMERCIAL 08/15/2002 COMPLETED Review Details
08/05/2002 RESUBMITTAL 08/15/2002 COMPLETED Review Details
08/28/2002 REVISION 09/06/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM03236
Permit Status: C of o
Permit Description: TI:MEDICAL OFFICE/ADDITION
Total Outstanding Activity Conditions - 1
Date Name
07/09/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T02CM03236
Permit Description: TI:MEDICAL OFFICE/ADDITION
Total Completed Inspections - 28
Date Description Inspector Results Comments
08/27/2002 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection 0000*
09/04/2002 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection 0000*
09/11/2002 ROOF NAILING AQUIROZ Approved IVRS - Inspection 0000*
09/25/2002 PLUMBING - ABOVE CEILING TRINIVJR Approved IVRS - Inspection 0000*1.) TRAP ARM FOR WASHER IN RM #150 DOSE NOT NOT MEET THE MIN. TRAP ARM DISTRANCE SEE SECTION:1002.2 94 UPC. 2.) STAND PIPE FOR WASHER DOSE NOT MEET MIN LENGTH SEE SECTION 804.1 94 UPC. 3.) RE TEST OR PROVIDE WATER TEST ON WASHER BOX ROUGH IN. 4.) OK TO DRYWALL ALL OTHER WALLS EXCEPT WASHER BOX AREA.
09/26/2002 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection 0000*
09/27/2002 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK A WASHER BOX. 2.) OK FOR DRYWALL.
09/27/2002 FRAMING AQUIROZ Approved IVRS - Inspection 0000*
10/11/2002 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection 0000*
10/11/2002 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection 0000*
10/21/2002 FIRE SPKLR - OH PIPING & HYDRO JEGAN Approved IVRS - Inspection 0000*PRESS TEST ONLY.
10/26/2002 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection 0000*WILL CHECK THERMAL FIRE BLANKETS ON TOP OF DIFFUSERS IN LAUNDRY ROOM ON FINAL. OK FOR CEILING TILES.
10/26/2002 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection 0000*
10/29/2002 FIRE SPKLR - UG, PIPING, HYDRO JEGAN Approved IVRS - Inspection 0000*UNDERGRD PRESS OKAY. NEED FLUSH.
11/04/2002 PLUMBING - FINAL FMCCLURE Approved IVRS - Inspection 0000*
11/04/2002 PLUMBING - ROUGH, SOIL FMCCLURE Approved
11/04/2002 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0000*OK C OF O.
11/04/2002 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection 0000*
11/04/2002 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection 0000*
11/07/2002 FIRE - FINAL LTHOMAS Approved
11/07/2002 FIRE SPKLR - FINAL LTHOMAS Approved
11/07/2002 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
11/12/2002 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0000*OK FOR C OF O.
11/12/2002 MECHANICAL - INTERMEDIATE JMILITEL Approved
11/12/2002 RIGHT OF WAY - FINAL PWHIDDON Approved
11/12/2002 SIGN - FINAL JYBARRA Approved NO SIGNS AT THIS TIME
11/12/2002 ENGINEERING - FINAL LMAKUS Approved
11/12/2002 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection 0000*OK C OF O.
11/20/2002 PERMIT FINALED AQUIROZ Approved