Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T02CM03236
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2002 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection 0000*1.) TRAP ARM FOR WASHER IN RM #150 DOSE NOT NOT MEET THE MIN. TRAP ARM DISTRANCE SEE SECTION:1002.2 94 UPC. 2.) STAND PIPE FOR WASHER DOSE NOT MEET MIN LENGTH SEE SECTION 804.1 94 UPC. 3.) RE TEST OR PROVIDE WATER TEST ON WASHER BOX ROUGH IN. 4.) OK TO DRYWALL ALL OTHER WALLS EXCEPT WASHER BOX AREA. | |
| 09/23/2002 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection 0999* |