Permit: T02CM03236

Parcel: 121136310


Addresses:

2255 N WYATT DR


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM03236

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
11/07/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*PROVIDE FIRE BLANKETS ON TOP OF SUPPLY & RETURN DIFFUSER/DAMPERS AS PER REVISED PLAN. DAMPER NOT COMPLETELY. OPEN IN RETURN DIFFUSER RECALL FOR INSPECTION.
11/04/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*PROVIDE OUTSIDE AIR VENTS.
PERMANENTLY LABEL EQUIPMENT. RAISE SEWER VENT 2' ABOVE OUTSIDE AIR INTAKE OR 10' AWAY. CONDENSATE TERMINATION S.E. CORNER OF ROOF MUST GO TO THE GROUND.