Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*WILL CHECK THERMAL FIRE BLANKETS ON TOP OF DIFFUSERS IN LAUNDRY ROOM ON FINAL. OK FOR CEILING TILES. |
| 10/22/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*PROVIDE LETTER FROM ENGINEER OR ARCHITECT DELETING FIRE DAMPER IN LAUNDRY ROOM. CHECKED FIRE DAMPER OPENINGS. OK TO INSTALL DAMPERS. |
| 10/18/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*INSPECTION ABOVE CEILING NORTH HALF OF BLDG. OK FOR CEILING TILES. NEED TO SEE FIRE DAMPER OPENINGS. DUCT SMOKE DETECTORS INSTALLED IN AC UNITS. |