Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T02CM03236

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK A WASHER BOX. 2.) OK FOR DRYWALL.
09/25/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
09/23/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) MUST STRAP DOWN ALL FUTURE WATE FEATURES 2.) LOTS OF UNISTRUT CLAMPS MISSING ON TRAPEEZES. 3.) MUST STRAP DOWN COPPER DROPS IN RMS 150,151, 4.) 1 1/2" DIRTY ARM EXCEEDS MAX DEVELOPED LENGHT 5.) MUST PROVIDE PERM SOLVE CAPS FOR ALL WASTE & VENTS THAT ARE TO BE CAPED. 6.) MUST PROVIDE TAPE OR POLY SLEEVE FOR COPPER DROPS & DISTRIBUTION IN RM 134. 7.) MUST PROVIDE HANGER ON HORIZONTAL VENT RM #101 VENT APPEARS TO HAVE BACK PITCH. 8.) MUST USE COPPER HANGERS FOR 2" COPPER MAIN. 9.) TWO WAY CO AND CONNECTION OF 3" BLDG. DRAIN TO EXSISTING BLDG. SEWER IS OK FOR BACKFILL.