Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
1100 S ALVERNON WY
Apply Date:
02/22/2002
Applicant:
GLHN ARCHITECTS AND ENGINEERS INC
Description:
NEW:MULTI SERVICE BUILDING
Contractors:
  • CONCORD COMPANIES INC

Permit Reviews

Permit Number - T02CM01019
Permit Status: C of o
Permit Description: NEW:MULTI SERVICE BUILDING
Start Date Submittal Complete Date Status  
01/16/2003 REVISION 01/25/2003 COMPLETED Review Details
02/09/2004 3RD PARTY REVIEW-REVISION/OTHER 02/10/2004 COMPLETED Review Details
02/18/2003 REVISION 02/25/2003 COMPLETED Review Details
02/22/2002 COMMERCIAL NEW 05/31/2002 COMPLETED Review Details
03/06/2003 REVISION 03/25/2003 COMPLETED Review Details
04/02/2003 3RD PARTY REVIEW-REVISION/OTHER 04/04/2003 COMPLETED Review Details
04/03/2003 3RD PARTY REVIEW-REVISION/OTHER 05/16/2003 COMPLETED Review Details
04/11/2003 3RD PARTY REVIEW-REVISION/OTHER 04/29/2003 COMPLETED Review Details
05/05/2003 3RD PARTY REVIEW-REVISION/OTHER 05/16/2003 COMPLETED Review Details
05/19/2003 3RD PARTY REVIEW-REVISION/OTHER 05/21/2003 COMPLETED Review Details
05/20/2003 3RD PARTY REVIEW-REVISION/OTHER 06/09/2003 COMPLETED Review Details
06/13/2003 3RD PARTY REVIEW-REVISION/OTHER 07/01/2003 COMPLETED Review Details
07/31/2003 REVISION 08/29/2003 COMPLETED Review Details
08/19/2003 3RD PARTY REVIEW-REVISION/OTHER 08/29/2003 COMPLETED Review Details
09/10/2003 3RD PARTY REVIEW-REVISION/OTHER 09/26/2003 COMPLETED Review Details
09/24/2002 RESUBMITTAL 10/09/2002 COMPLETED Review Details
10/14/2003 3RD PARTY REVIEW-REVISION/OTHER 10/30/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM01019
Permit Status: C of o
Permit Description: NEW:MULTI SERVICE BUILDING
Total Outstanding Activity Conditions - 1
Date Name
02/22/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T02CM01019
Permit Description: NEW:MULTI SERVICE BUILDING
Total Completed Inspections - 42
Date Description Inspector Results Comments
12/17/2002 STEM WALL/RETAINING WALL LHANLY Approved IL GRID 10 TO 15.5.
RFI #28 GIVES REPAIR DATA FOR NOTE DATED 12-5-02 RE: HEAD WALL EXTENSIONS.
12/17/2002 STEM WALL/RETAINING WALL LHANLY Approved IVRS - Inspection 0000*
12/19/2002 ELECTRIC - UNDERGROUND MCAPISTR Approved IVRS - Inspection 0000*
1.) TWO 4" PVC FOR COMM.
2.) U/G BOX TO POLE SITE.
12/30/2002 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection 0000*
1.) IN MASONARY WALLS CONDUIT ELECT SECTION OK TO CONTINUE USE APPROVED FITTINGS AND BOXES WITH CONDUIT.
12/30/2002 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection 0000*TOP 15.5 - 12.5 EAST WALL IL EAST WALL 6-9.
12/31/2002 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection 0000*/ 1) COMPLETE VOULT FOOTINGS AREA B6 2) RETAIN FOOTING FOR RAMP AT D.7/S.5-9 INCLUDING RAMP FOOT LINE 7 ALSO LINE S.5/D-E EXCLUDING CORNER AT DS.5
01/23/2003 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection 0000*20'PLUS 350 MCM UFER.
02/05/2003 PLUMBING - ROUGH, SOIL TRINIVJR Approved 1.) 2" WASTE LINE FOR SINK FROM GRID LINE #9 WEST TO #12 IS OK
2.) FLOOR DRAINS BETWEEN GRID #4 & 5 WEST TO #12 IS OK
3.) OK TO BACKFILL TRENCH.
03/21/2003 FIRE SPKLR - UG, PIPING, HYDRO JEGAN Approved IVRS - Inspection 0000*
03/24/2003 PLUMBING - YARD WTR LINE/TEST TRINIVJR Approved IVRS - Inspection 0000*
1.) YARD WATER LINE IS OK AS PER INITALS ON PLAN.
2.) OK TO BACKFILL TRENCH.
3.) WILL REQUIRE A AIR TEST ON 3" WATER SERVICE @ A LATER TIME.
05/05/2003 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved IVRS - Inspection 0000*AIR PRESSURE TEST FOR DCW IS OK UP TO SEWER EJECTOR ONLY.
2.) OK TO STACK M.H.
07/03/2003 BUILDING PRE-SLAB AMATHIES Approved IVRS - Inspection 0000*
07/30/2003 PLUMBING - GAS PRESSURE TEST TRINIVJR Approved 1) GAS PRESSURE TEST IS OK 2) THIS INSPECTION IS FOR ALL GAS LINE DOWNSTREAM OF WELDED SYSTEM ONLY
08/08/2003 FIRE SPKLR - UG PIPING FLUSH JEGAN Approved IVRS - Inspection 0000*/ 1) PARTIAL UNDERGROUND PRESSURE TEST OK (STILL NEED TEST/FLUSH WHEN ALL IS TIED TOGETHER)
09/04/2003 BUILDING - FINAL AMATHIES Approved IVRS - Inspection 0000* OK FOR TEMP C/O
09/09/2003 SHEET ROCK NAILING AMATHIES Approved
09/09/2003 FRAMING AMATHIES Approved
09/09/2003 EXT METAL CLIPS/EXT SHEATHING AMATHIES Approved
09/30/2003 MECHANICAL - TEMP PWR FOR TEST CWILLIAM Approved IVRS - Inspection 0000*
09/30/2003 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection 0000*/ 1) 2ND FLOOR SOUTH END EAST/WEST CORNER 2) OK TO INSULATE
09/30/2003 PLUMBING - TEMP POWER FOR TEST JSTANLEY Approved IVRS - Inspection 0000*
09/30/2003 BUILDING - TEMP POWER FOR TEST AMATHIES Approved IVRS - Inspection 0000*
10/10/2003 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection 0000*/ WORK IS COMPLETE AND FINAL FOR THE 3753 E 22ND ST ADDRESS. / 1100 S ALVERNON WAY ADDRESS: H2O PIPING MAIN TO S-102 IN 2103, S-102 IN 2026 AND EWF P-402 IN 2095 - ALL OK.
10/13/2003 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection 0000*
10/22/2003 PLUMBING - GAS PRESS TEST FNL TRINIVJR Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) THIS INSPECTION IS FOR 3" GAS LINE FROM BOILER ROOM TO METER LOCATION IS OK
11/03/2003 STUCCO MESH LHANLY Approved IVRS - Inspection 0000* 1) HOLDING CELLS CEILINGS & WALLS OK. 2) SOUTH ENTRY LID OK
11/13/2003 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
11/18/2003 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection 0000*/ 1) TEMP C OF O OK, WHEN ALL PROPER PAPERWORK PROCESSED
11/26/2003 PLUMBING - FINAL TRINIVJR Approved 3753 E. 22ND ST - FINAL APPROVED - NO PLBG AT THIS ADDRESS. / 1100 S. ALVERNON - PARTIAL APPROVAL - 1) 1ST FLOOR MENS AND WOMENS RESTROOM IN SWAT AREA ARE UP AND IN WORKING ORDER. 2) OK FOR TEMP C OF O AS PER STEVE LONG.
12/02/2003 ELECTRIC - TEMP POWER FOR TEST JORTA Approved SENT TO TEP 1203AM
12/02/2003 ELECTRIC - ABOVE CEILING JORTA Approved IVRS - Inspection 0000*/ ALL 'K' FIXTURE WIRING/INSTALLATION APPROVED. NEED TEST INSTRUCTION BOOKLET FROM SQUARE D TO COMPLETE TEST PROCEDURE REQUIREMENT PER CODE. THIS WILL IN TURN BE APPROVED BY SUPERVISOR AN ELEC. PLANS EXAMINER AT OFFICE. OK TEMP C OF O FOR FURNITURE AND STOCKING - NOT TO OCCUPY.
12/04/2003 FIRE - FINAL JEGAN Approved IVRS - Inspection 0000*
12/04/2003 FIRE SPKLR - FINAL JEGAN Approved IVRS - Inspection 0000*/ 1) OK C OF O
01/21/2004 ELECTRIC - FINAL JORTA Approved IVRS - Inspection 0000*
01/21/2004 ELECTRIC - CABLE DROP JORTA Approved
02/02/2004 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection 0000*
02/11/2004 RIGHT OF WAY - FINAL MOTERO Approved
02/18/2004 LANDSCAPE - FINAL ACONNOR Approved Addition landscape inspection needed when hydrseeding is complete.
03/23/2004 OUTDOOR LIGHTING FINAL JORTA Approved IVRS - Inspection 0000*
06/14/2004 ENGINEERING - FINAL DROBERTS Approved
06/29/2004 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
07/15/2004 PERMIT FINALED AMATHIES Approved