Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM01019
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2004 | ELECTRIC - INTERMEDIATE | Approved | ||
10/13/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) HOLDING SECURITY AREA | |
09/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) SALLYPORT WALLS, INTERMEDIATE APPROVED 2) TRANSFORMER GROUNDING T.A., AND T.E. COMPLETE. ABOVE TRANSFORMERS APPROVED 3) MAIN GROUNDING ELECTRODE SYSTEM; UFER, WATER AND BLDG STEEL COMPLETE AND APPROVED. WILLNEED GAS BOND 4) WILL NEED PERFORMANCE TESTING (FOR POWER) IN EXACT COMPLIANCE WITH 230-95 1999 NEC | |
09/10/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) FOR TEMP POWER: NEED LETTER OF TORQUING PER MANUFACTURERS SPECIFICATION ON SES, LDS, TRTE, TRTA, PANELS EMG, DISC. EMP1, PANELS HPP, HPL, HPM, MNP1, LDS 2) NEED GFI TEST PER 230.95 3) NEED INSPECTOR SIGN OFF SHEET COMPLETED 4) NEED PROPER ILLUMINATION FOR SES 5) ALL SERVICES AND TRANSFORMER GROUNDING | |
09/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ "SERVICE ONE LINE" T.E. T.R. REQUIRED GROUND ELECTRODE - STEEL GROUND. DISC. T.E. APP. PNL H.P.P. ONE LINE APP. PNL H.P.L. FEEDER/MAIN ONE LINE APP. PNL H.P.N. ONE LINE APP. PNL. M.N.P.I. ONE LINE APP. TR. T.A. NEEDS REVISIONS ON SIZING AND PARTIAL. NEEDS BUILD STEEL. | |
09/08/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ FOR S.E.S. NEED PERMANENT TAGS. NEED PERFORMANCE TESTING PER 230-95. ENCLOSE C.T. METERING WIRING TO SUPPLY CUBICLE. NEED LETTER OF TORQING WITH COMPANY LETTERHEAD. | |
08/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ROOMS 2109, 2110, 2108, 2107, 2026, 2022, 2023, 2026, 2027, 2028, 2081, 2082 AND 2168 | |
08/15/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 2013, 2002, 2003, 2005, 2006 | |
08/08/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ROOMS 2010, 2018, 2036, 2038 AND 2112 2) 2007 B,C,D OK TO COVER | |
07/31/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
07/31/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
07/30/2003 | ELECTRIC - INTERMEDIATE | Denied | 1) NO ONE AT SITE | |
07/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
07/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL GRID 3 TO 6 AND B TO A | |
07/18/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ CANCELLED | |
07/15/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL APPROVAL FOR ROOMS; 2064, CORRIDOR 2063 (FROM ELEVATOR). 2057, 2058, 2059 2060, 2049, 2050, 2051, 2068, 2052, 2053, 2054, 2056 AND DE BRIEFING2045; NOT PANEL NENP IN VIOL. OF 110.26 SPRINKLER LINE | |
06/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/EAST OF GRID A; BETWEEN GRID 10 AND 5.5 WALL APPROVED (STUD) | |
12/30/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1.) IN MASONARY WALLS CONDUIT ELECT SECTION OK TO CONTINUE USE APPROVED FITTINGS AND BOXES WITH CONDUIT. |