Permit: T02CM01019

Parcel: 12620001A


Addresses:

1100 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM01019

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/21/2004 ELECTRIC - INTERMEDIATE Approved
10/13/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) HOLDING SECURITY AREA
09/23/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) SALLYPORT WALLS, INTERMEDIATE APPROVED 2) TRANSFORMER GROUNDING T.A., AND T.E. COMPLETE. ABOVE TRANSFORMERS APPROVED 3) MAIN GROUNDING ELECTRODE SYSTEM; UFER, WATER AND BLDG STEEL COMPLETE AND APPROVED. WILLNEED GAS BOND 4) WILL NEED PERFORMANCE TESTING (FOR POWER) IN EXACT COMPLIANCE WITH 230-95 1999 NEC
09/10/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) FOR TEMP POWER: NEED LETTER OF TORQUING PER MANUFACTURERS SPECIFICATION ON SES, LDS, TRTE, TRTA, PANELS EMG, DISC. EMP1, PANELS HPP, HPL, HPM, MNP1, LDS 2) NEED GFI TEST PER 230.95 3) NEED INSPECTOR SIGN OFF SHEET COMPLETED 4) NEED PROPER ILLUMINATION FOR SES 5) ALL SERVICES AND TRANSFORMER GROUNDING
09/09/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ "SERVICE ONE LINE" T.E. T.R. REQUIRED GROUND ELECTRODE - STEEL GROUND. DISC. T.E. APP. PNL H.P.P. ONE LINE APP. PNL H.P.L. FEEDER/MAIN ONE LINE APP. PNL H.P.N. ONE LINE APP. PNL. M.N.P.I. ONE LINE APP. TR. T.A. NEEDS REVISIONS ON SIZING AND PARTIAL. NEEDS BUILD STEEL.
09/08/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ FOR S.E.S. NEED PERMANENT TAGS. NEED PERFORMANCE TESTING PER 230-95. ENCLOSE C.T. METERING WIRING TO SUPPLY CUBICLE. NEED LETTER OF TORQING WITH COMPANY LETTERHEAD.
08/21/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) ROOMS 2109, 2110, 2108, 2107, 2026, 2022, 2023, 2026, 2027, 2028, 2081, 2082 AND 2168
08/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 2013, 2002, 2003, 2005, 2006
08/08/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) ROOMS 2010, 2018, 2036, 2038 AND 2112 2) 2007 B,C,D OK TO COVER
07/31/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
07/31/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
07/30/2003 ELECTRIC - INTERMEDIATE Denied 1) NO ONE AT SITE
07/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
07/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) PARTIAL GRID 3 TO 6 AND B TO A
07/18/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ CANCELLED
07/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) PARTIAL APPROVAL FOR ROOMS; 2064, CORRIDOR 2063 (FROM ELEVATOR). 2057, 2058, 2059 2060, 2049, 2050, 2051, 2068, 2052, 2053, 2054, 2056 AND DE BRIEFING2045; NOT PANEL NENP IN VIOL. OF 110.26 SPRINKLER LINE
06/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/EAST OF GRID A; BETWEEN GRID 10 AND 5.5 WALL APPROVED (STUD)
12/30/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1.) IN MASONARY WALLS CONDUIT ELECT SECTION OK TO CONTINUE USE APPROVED FITTINGS AND BOXES WITH CONDUIT.