Permit: T02CM01019

Parcel: 12620001A


Addresses:

1100 S ALVERNON WY


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM01019

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/11/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS MADE. COPIED OF BACKFLOW CERTIFICATIONS [7], COPY OF CLORINATION AND BACTERIA REPORT [1], COPY OF BOILER INSPECTION REPORT [1].
02/05/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) INDIRECT WASTE IN JANITOR SINK 1016 TO HAVE 1" AIR GAP 2) WAITING ON CITY APPROVED DRAWING FOR 4" FLOOR SINK AT COOLING TOWER ARCH INTO MANHOLE
01/30/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) URINAL FLUSH VALVE TO HAVE 6" CRITICAL LEVOR FROM TOP OF FIXTURE. 2) NEED COPIES OF ALL BACKFLOW PREVENTION REPORTS AND CLORINATION REPORT. 3) 1" AIR GAP AT ALL INDIRECT WASTE FIXTURES. 4) COOLING TOWER DRAINS TO GO TO APPROVED WASTE RECEPTOR. 5) BACK FLOW DEVICE FOR MAKE-UP TO BOILER NEED DRAIN TERMINATION. 6) HOSE REELS H20 SUPPLY TO BE PROVIDED WITH BACKFLOW PROTECTION.
01/21/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) ALL DRAINS AT COOLING TOWER SHALL GO TO INDIRECT WASTE RECEPTOR 2) BACK FLOW CERTIFICATIONS AND CHLORINE CERTIFICATION DOCUMENTS AT TIME OF FINAL 3) BACK FLOW DEVICE FOR HEATING WATER SYSTEM TO BE PIPED 80 FLOOR SINK 4) STATE BOILER INSPECTOR CERTIFICATION OF BOILER 5) ALL WATER USING SYSTEMS REQUIRE 1" AIR GAP OR BACKFLOW PROTECTION
11/26/2003 PLUMBING - FINAL Partial Approval 3753 E. 22ND ST - FINAL APPROVED - NO PLBG AT THIS ADDRESS. / 1100 S. ALVERNON - PARTIAL APPROVAL - 1) 1ST FLOOR MENS AND WOMENS RESTROOM IN SWAT AREA ARE UP AND IN WORKING ORDER. 2) OK FOR TEMP C OF O AS PER STEVE LONG.
11/24/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*