Permit: T01CM01124
Permit Details
Apply Date:
03/07/2001
Applicant:
SMITH, DONALD EUGENE
Description:
NEW:SCHOOL
Architects:
- SMITH, DONALD EUGENE
Contractors:
- COOKIES CONSTRUCTION COMPANY ,
Permit Reviews
Permit Number - T01CM01124
Permit Status: C of o
Permit Description: NEW:SCHOOL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/07/2001 | COMMERCIAL NEW | 04/12/2001 | COMPLETED |
| 04/12/2001 | RESUBMITTAL | 10/29/2001 | COMPLETED |
| 04/16/2001 | SITE | 04/24/2001 | COMPLETED |
| 09/26/2002 | REVISION | 10/17/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01CM01124
Permit Status: C of o
Permit Description: NEW:SCHOOL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/07/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T01CM01124
Permit Description: NEW:SCHOOL
Total Completed Inspections - 41
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/26/2001 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) NOTE: BLDG. DRAINS ARE STUBBED OUT OF BLDG ONLY 3.) OK TO BACKFILL TRENCH. |
| 12/31/2001 | BUILDING PRE-SLAB | AMATHIES | Approved | IVRS - Inspection 0000* |
| 12/31/2001 | EXCAVATION/LAYOUT REBAR & ZON | AMATHIES | Approved | IVRS - Inspection 0000* |
| 01/02/2002 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection 0000*2" PVC SERVICE TO PANEL INSIDE 8-3/4" PVC STUBBS OUT OF BLDG. |
| 01/18/2002 | PLUMBING - SEWER HCS CONNECT | JSTANLEY | Approved | IVRS - Inspection 0000*TEST OK ON SITE SEWER OK TO BACK FILL PLEASE HAVE PLUMBER REMOVE BLAKE TEC. |
| 03/06/2002 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 03/27/2002 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 05/02/2002 | PLUMBING - YARD WTR LINE/TEST | JSTANLEY | Approved | IVRS - Inspection 0000* 2 1/2" SITE WATER OK. |
| 06/03/2002 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 06/06/2002 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000* |
| 06/07/2002 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) GAS PRESSURE TEST IS OK 4.) OK TO DRYWALL UPON BLDG. INSPECTORS APPROVAL. |
| 06/07/2002 | FRAMING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 06/19/2002 | SHEET ROCK NAILING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 07/03/2002 | MECHANICAL - TEMP PWR FOR TEST | JMILITEL | Approved | IVRS - Inspection 0000* |
| 07/03/2002 | PLUMBING - TEMP POWER FOR TEST | TRINIVJR | Approved | IVRS - Inspection 0000*GAS & WATER LINE HAS BEEN BONDED. |
| 07/03/2002 | BUILDING - TEMP POWER FOR TEST | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 07/05/2002 | ELECTRIC - TEMP POWER FOR TEST | DSANTACR | Approved | IVRS - Inspection 0000*OK TO CLEAR TEMP POWER FOR TEST. NOTES ELECTRICAL CONTR. WILL KEEP PANEL BOARDS LOCKED, HAS KEY AND AND PANEL SIGNED POSTED. |
| 07/25/2002 | PLUMBING - ABOVE CEILING | TRINIVJR | Approved | IVRS - Inspection 0000*1.) ABOVE CEILING IS OK. 2.) OK FOR GRID. |
| 07/25/2002 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection 0000*NOTES 1.) INSTALL BOND BUSHING WHERE USING CONCENTRIC KO'S PER 250-94. 2.) INSTALL SEALING LOCKNUT ON 1/2" EMT TERMINATED AT TOP OF PANEL. 3.) USE MIN 1/4" BOLTS TO SUPPORT RISER. |
| 07/25/2002 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 07/26/2002 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection 0000*HOOK UP DUCT TO EXHAUST FAN IN MEN'S ROOM. REPAIR BROKEN PANDUIT STRAP ON DUCT CLASS ROOM 1 STRAP DUCT W/ 1 1/2 STRAP. NOT PANDUIT STRAP. WILL CHECK ON FINAL. |
| 08/21/2002 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0000*OK FOR C OF O |
| 08/21/2002 | PLUMBING - GAS PRESSURE TEST | TRINIVJR | Approved | IVRS - Inspection 0000*PLBG. FINAL IS OK 2.) OK C OF O. |
| 08/21/2002 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection 0000*OK C OF O. |
| 08/21/2002 | ELECTRIC - CABLE DROP | DSANTACR | Approved | |
| 08/21/2002 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | |
| 08/23/2002 | RIGHT OF WAY - FINAL | DLEE | Approved | TEMP ONLY PENDING COMPLETION OF SIDEWALK |
| 08/23/2002 | ENGINEERING - FINAL | LMAKUS | Approved | TEMPORARY C OF O APPROVED. FINAL NOT TO BE GIVEN UNTIL THE FINAL GRADING INSPECTION #9190 FOR T01BU01157 HAS BEEN COMPLETED AND ACCEPTED. |
| 08/23/2002 | PLUMBING - FINAL | TRINIVJR | Approved | IVRS - Inspection 0000* |
| 08/23/2002 | PLUMBING - PROGRESS | TRINIVJR | Approved | |
| 08/23/2002 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection 0000*OK TEMP C OF O. |
| 08/26/2002 | NPPO - FINAL | PGILBERT | Approved | OK TEMP C OF O. REQUESTED MONITORING REPORT. |
| 08/26/2002 | LANDSCAPE - FINAL | PGILBERT | Approved | OK TEMP C OF O. REQUESTED MONITORING REPORT. |
| 08/26/2002 | FIRE - FINAL | LTHOMAS | Approved | |
| 08/26/2002 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
| 08/26/2002 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 08/26/2002 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 08/26/2002 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 08/26/2002 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 08/27/2002 | SIGN - FINAL | DJOHNSTO | Approved | IVRS - Inspection 0000* |
| 02/19/2004 | PERMIT FINALED | AMATHIES | Approved |