Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM01124

Parcel: 121110660

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/21/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O
08/07/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) REBUILD CONDENSATE TRAPS PE MANUFACTURES SPECS. BLOCK & CLAMP DRAIN LINES. 2.) GAS FLEX CONNECTOR MUST BE INSTALLED AT THE INLET ON FURNACE & VALVE NO THAN 3' FROM INLET. BLOCK & CLAMP GAS PIPE 3.) RAISE SEWER VENTS 2' ABOVE AIR INTAKES ON A/C UNITS. 4.) NEED TO SEE WATER HEATER VENT CONNECTOR INSTALLED. RECALL FOR FINAL.