Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O |
| 08/07/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) REBUILD CONDENSATE TRAPS PE MANUFACTURES SPECS. BLOCK & CLAMP DRAIN LINES. 2.) GAS FLEX CONNECTOR MUST BE INSTALLED AT THE INLET ON FURNACE & VALVE NO THAN 3' FROM INLET. BLOCK & CLAMP GAS PIPE 3.) RAISE SEWER VENTS 2' ABOVE AIR INTAKES ON A/C UNITS. 4.) NEED TO SEE WATER HEATER VENT CONNECTOR INSTALLED. RECALL FOR FINAL. |