Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/25/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*NOTES 1.) INSTALL BOND BUSHING WHERE USING CONCENTRIC KO'S PER 250-94. 2.) INSTALL SEALING LOCKNUT ON 1/2" EMT TERMINATED AT TOP OF PANEL. 3.) USE MIN 1/4" BOLTS TO SUPPORT RISER. |
| 06/03/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*OK HARD LIDS ONLY AND WALLS OUTSIDE SOFFITS 5000E. |