Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/07/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) GAS PRESSURE TEST IS OK 4.) OK TO DRYWALL UPON BLDG. INSPECTORS APPROVAL. |
| 06/06/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY FOR INSPECTION. |
| 06/03/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST ON WASTE AND VENT SYSTEM ALL THE WAY TO THE TOP OF VENTS THRU ROOF SEE SECTION: 712.2 94 UPC. 2.) DIRTY ARM FOR DRINKING FOUNTAIN CAN ONLY HAVE 1-90 SEE SECTION 1002.3 94 UPC 3.) REVENT FOR DRINKING FOUNTAIN HAS BACK PITCH @ HORIZONTAL. 4.) 1 1/4" GAS LINE DOES NOT HAVE ANY MARKINGS ON PIPE SEE SECTION 301.1.2. 94 UPC. 5.) TRAP ARMS FOR P-4 REQUIRES A 2" TRAP. TRAP MUST BE THE SAME SIZE AS TRAP ARM SEE SECTION: 1003.3 94 UPC. 6.) CLOSET RINGS HAVE NOT BEEN INSTALLED. |