Permit: T01CM01124

Parcel: 121110660

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/23/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
08/21/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST CAULK BOTH DRINKING FOUNTAINS 2.) H.C. LAVATORY IN MEN RESTROOM MUST BE NO HIGHER THAN 34" AFF FROM TOP OF LAV AND 29" FROM F.F. TO BOTTOM OF LAV ADA SPECS. 3.) MUST STRAP DOWN EXPANSION TANK @ WATER HTR. 4.) (1) CLASSROOM SINK NOT COMPLETE. 5.) MUST PERM CAP ALL GRADE C.O. NO JIM CAPS ACCEPTED.