Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/18/2006

Applicant:

TUPART II LLC

Description:

Full fire prevention inspection.

Outstanding Inspections

Case Number: T06FR02900
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
12/18/2006 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ***Remove storage to 18 inches or more below sprinkler head. {Arange lockers so there is at least 18 inches of clearance.}
12/18/2006 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.4 Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure.Awritten record shall be maintained and be available to the fire code official. ***All fire doors in stock room need service test.
12/19/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3.1 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ***Provide such signage for electrical service rooms.
12/19/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ***Remove noncomplying devices. {In stock room electrical room, phone power cords pluged into power strip, pluged into another power strip.}
12/19/2006 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. ***Sprinkler escutcheon shall be replaced in kitchen.
12/19/2006 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress. ***Emergency egress lighting shall be comply with this section. {In stock room,West side electrical room}.
12/19/2006 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. 2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller’s warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct the required means of egress. 4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use. ***Secure carbon dioxide bottles in kitchen. Re-inspection scheduled on or after 1/10/07. Call Inspector John Bieg at 791-4502, if you have any further questions.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02900
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/18/2006 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: