Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T06FR02900

Parcel: 13322424B


Addresses:

7055 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - COMPRESSED GASES

Case Number - T06FR02900

Inspection Description - VIOL - COMPRESSED GASES

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/19/2006 VIOL - COMPRESSED GASES Correction Required TFC 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods:
1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.
2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller’s warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct
the required means of egress.
4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use.
***Secure carbon dioxide bottles in kitchen.


Re-inspection scheduled on or after 1/10/07.
Call Inspector John Bieg at 791-4502, if you have any further questions.