Case: T06FR02900

Parcel: 13322424B


Addresses:

7055 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR02900

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/19/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
***Sprinkler escutcheon shall be replaced in kitchen.
12/18/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
***Extinguisher by west side garden exit shall be accessable.
12/18/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.
***Remove wood planks from over conveyer belt. {upstairs storage}.