Case: T06FR02900

Parcel: 13322424B


Addresses:

7055 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR02900

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/19/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3.1 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.
***Provide such signage for electrical service rooms.
12/19/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4.2 Power supply. Relocatable power taps shall be directly
connected to a permanently installed receptacle.
***Remove noncomplying devices. {In stock room electrical room, phone power cords pluged into power strip, pluged into another power strip.}
12/18/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
***Place an approved "blank" in the electric panel by the customer service center. (In the electrical room.)
***Light in south, middle entrance is broken and hanging down from the ceiling. {Repair light}.
12/18/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
***Cover wires in an approved manner. (In the cash count room.)
***Open wire boxes/ splices: (Garden area NW side). Cover wires in open electrical box in an approved manner.
12/18/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
***Extension cord behind soda machine, in the middle intrance, shall be removed or replace with approved power strip.
***Extension cord through ceiling by far east entrance shall be removed.
***Extension cord through ceiling tile by garden entrance shall be removed.
***In HR copier room remove the extension cord and cube adapter, replace them with a fused power strip.
***Remove extension cord and replace with a fused power strip. {Pharmacy, south west side}.
***Extension cords: (near TV on pillar in electronics). Replace with a fused power strip.
***Extension cords: (HR Training room). Replace with a fused power strip.
***Remove extension cord through ceiling {runing to Pepsi machine in layaway area}.
***Extension cord through ceiling shall be removed, {in kitchen}.
***Extension cord through ceiling shall be removed, { over west entrance isle}.
12/18/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
***In employee lunch room remove cube adapter and replace with a fused power strip.