Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

09/28/2005

Applicant:

CHICAGO STORE LTD PARTNERSHIP

Description:

Inspection

Outstanding Inspections

Case Number: T05FR01520
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 46
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
09/26/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy.
09/26/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be mainained at least 18" below ceiling in sprinklered areas and 24" below ceiling in unsprinklered areas.
09/26/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 316.1- Clearance from combustible materials shall be maintained for all heat producing appliances. (heater upstairs)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 603.9- Gas piping shall be protected in an approved manner. (S wall outside)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Electrical to receptacle box shall be protected. (small drum window)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Electrical to receptacle over doorway shall be protected. (music store)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. A grounded application shall not be connected by means of an ungrounded adapter. (N side)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Light bulb fixture shall be abated. (upstairs)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment.
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3.1- Doors to electrical panel shall be marked with the words "ELECTRIC PANEL". (NE corner)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters shall be prohibited.
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4.1- Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. (small drum window)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle.
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. (studio)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords (N side, upstairs)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall be prohibited.
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (N wall, several)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be used as permanent wiring. (S wall outside)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes shall be prohibited. (electrical panel in NE corner)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes shall be prohibited. (N window front)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes shall be prohibited. (studio)
09/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC Extension cords shall not be used as permanent wiring. (basement)
09/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually. (upstairs)
09/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishing systems shall be serviced annually. Last sprinkler system test was 6-14-02.
09/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 903.2.6- An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where a Group M fire area exceeds 12,000 Square feet. *With the addition and penetrations to 128 E Congress, the gross floor area is approximately 13,400 square feet.
09/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (top of stairwell)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Exit doors are blocked by piano. (music store)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Exits shall not be blocked. (NE exit door)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Pathway to exit shall not be interrupted. (upstairs, NE stairwell)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Pathways shall not be interrupted.
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Pathways shall not be interrupted. (upstairs)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Stairwell blocked. (outside studio)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Stairwell was blocked (NW side)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- The path of egress travel along a means of egress shall not be interrupted. (N exit and path, pathways throughout)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- Emergency illumination required. (music store)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- Emergency lighting for basement and stairwell is required.
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- In the event of a power failure, an emergency electrical system shall automatically illuminate the following areas: 1. passageways an aisles in rooms and spaceswhich require 2 or more means of egress 2. exit stairways located in buildings requiring 2 or more exits 3. interior exit discharge elements 4. the portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have 2 or more exits
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.9- Where panic and fire exit hardware are installed, the maximum unlatching force shall be 15 pounds.
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.1- Exits shall be marked with an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or path of egress travel is not immediately visible to the occupants.
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Exit signs shall be illuminated at all times. (basement)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Exit signs shall be illuminated at all times. (music store)
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1014.2- Exits shall be unobstructed at all times. The rear (S) exit is a required exit.
09/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1026.17.2- For an M occupancy, the maximum travel distances are as follows: Common Path Limit = 75 feet Dead End Limit = 50 feet Travel Distance to an Exit = 200 feet
09/26/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.1.1(1)- The maximum allowable quantity for flammable liquids is 30 gallons, 60 if stored in an approved cabinet.
09/26/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured from accidental dislodgement. (storage)

Completed Inspections

Case Status: FIELD
Case Number: T05FR01520
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/24/2006 INSP - REINSPECTION JLANGEJA Approved A reinspection of the premises showed that most items have not been corrected that were issued with the pre-citation. There were many other new violations, mostly with electrical and egress issues. Owner was informed that this was going to city legal. I took pictures of each violation.